-- * APC cPDU SNMP MIB DEFINITIONS
-- * $Date: 8 MAY 2025 06:00:00 $
-- * $Revision: 1.9 $
--   Revised 
--   -> Line to Line OID addition
-- ****************************************************************************
-- * APC cPDU SNMP MIB DEFINITIONS
-- * $Date: 27 AUGUST 2024 09:00:00 $
-- * $Revision: 1.8 $
--   Revised 
--   Confidential - Need To Know
-- ****************************************************************************
--
--      APC cPDU SNMP 
--      Management Information Base for SNMP Network Management for PDU
--
--      Copyright (c) 2021 APC
--
--      The APC Enterprise number is 318.
--      The ASN.1 prefix to, and including the APC is:
--           1.3.6.1.4.1.318
--
--      MIB Version 1.7
--
--    *********************************************************************
--    Release History
--		
-- 		Added following OIDs to mib table.(27 AUGUST 2024)
--		-> pduUnitConfigUsb - Displays/Configures USB status enbaled or disabled.
--		-> pduUnitConfigDaisyChainState - Displays/Configures Daisychain state as QNA or RNA.
--		-> pduUnitConfigTelnet - Displays/Configure status of Telnet feature as ON or OFF.
--		-> pduUnitPsSupportUpstreamStatus - Deprecated.
--		-> pduUnitPsSupportDownstreamStatus - Deprecated.
--		-> pduUnitPsFunc - Displays/Configures Power Share Functionality as Enable or Disable.
--		-> pduUnitPsBackupProtection - Displays Power Share support status from adjacent PDUs.
--		-> pduUnitPsOutput - Displays Power Share support status to adjacent PDU.
--		-> pduExternalSensorConfigAlarmResetThreshold - Displays/Configures sensors reset threshold value.
--		-> pduExternalSensorConfigAlarmStateChangeDelay - Displays/Configures sensors state change delay value.
--		-> pduExternalSensorSTATUSAisle - Displays Aisle status as hot or cold.
--
-- 		Added following OIDs to mib table.
--		-> pduNamePlateIPV6Address - Displays both Local and Global address of IPV6.
--		-> pduNamePlateHWVersion - Displays Hardware version of the PDU.
--      -> pduUnitStatusPowerFactor - Displays Power Factor value of total PDU.
--		-> pduCircuitBreakerStatusPowerFactor - Displays Power Factor value of circuit breaker.
--		-> pduInputPhaseStatusPowerFactor - Displays Power Factor value of each Phases.
--    *********************************************************************
-- ===================================================================================
-- sysDescr (1.3.6.1.2.1.1.1) which is defined in RFC1213.MIB.
-- sysObjectID (1.3.6.1.2.1.1.2) which is defined in RFC1213.MIB.
-- sysContact (1.3.6.1.2.1.1.4) which is defined in RFC1213.MIB.
-- sysName (1.3.6.1.2.1.1.5) is which is defined in RFC1213.MIB.
-- sysLocation (1.3.6.1.2.1.1.6) which is defined in RFC1213.MIB.
-- 
-- sysDescr OBJECT-TYPE
--     SYNTAX  DisplayString (SIZE (0..255))
--     ACCESS  read-only
--     STATUS  mandatory
--     DESCRIPTION
--             "A textual description of the entity.  This value
--             should include the full name, hardware version and
--             firmware version of management module's.
--             It is mandatory that this only contain
--             printable ASCII characters."
--     ::= { system 1 }
--
-- sysObjectID OBJECT-TYPE
--     SYNTAX  DisplayString (SIZE (0..255))
--     ACCESS  read-write
--     STATUS  mandatory
--     DESCRIPTION
--             "Return the OID of the management module for PDU defined in the APC.MIB
--             i.e. .1.3.6.1.4.1.318.1.1.32 is for OIDs."
--     ::= { system 2 }
--
-- sysContact OBJECT-TYPE
--     SYNTAX  DisplayString (SIZE (0..255))
--     ACCESS  read-write
--     STATUS  mandatory
--     DESCRIPTION
--             "The textual identification of the contact person
--             for this managed node, together with information
--             on how to contact this person."
--     ::= { system 4 }
--
-- sysName OBJECT-TYPE
--     SYNTAX  DisplayString (SIZE (0..255))
--     ACCESS  read-write
--     STATUS  mandatory
--     DESCRIPTION
--             "An administratively-assigned name for this
--             managed node.  By convention, this is the node's
--             fully-qualified domain name."
--     ::= { system 5 }
--
-- sysLocation OBJECT-TYPE
--     SYNTAX  DisplayString (SIZE (0..255))
--     ACCESS  read-write
--     STATUS  mandatory
--     DESCRIPTION
--             "The physical location of this node (e.g.,
--             `telephone closet, 3rd floor')."
--     ::= { system 6 }
--
-- ====================================================================================
--
-- ====================================================================================
PowerNet-MIB DEFINITIONS ::= BEGIN

IMPORTS
   enterprises, IpAddress, Gauge, TimeTicks             FROM RFC1155-SMI
   DisplayString, sysDescr                              FROM RFC1213-MIB
   SnmpAdminString                                      FROM SNMP-FRAMEWORK-MIB
   OBJECT-TYPE                                          FROM RFC-1212
   TRAP-TYPE                                            FROM RFC-1215
   InetAddressType                                      FROM INET-ADDRESS-MIB
   InetAddress                                          FROM INET-ADDRESS-MIB
   MacAddress                                           FROM SNMPv2-TC;
-- IMPORTS End

apc						OBJECT IDENTIFIER 		::= { enterprises 318 }

products				OBJECT IDENTIFIER 		::=  { apc 1 }

hardware				OBJECT IDENTIFIER 		::=  { products 1 }

cPDU					OBJECT IDENTIFIER 		::=  { hardware 32 }
-- ++++ Start of cPDU ++++

pduNamePlate			OBJECT IDENTIFIER       ::= { cPDU 1 }
pduUnit					OBJECT IDENTIFIER       ::= { cPDU 2 }
pduInputPhase			OBJECT IDENTIFIER       ::= { cPDU 3 }
pduCircuitBreaker		OBJECT IDENTIFIER       ::= { cPDU 4 }
pduOutlet				OBJECT IDENTIFIER       ::= { cPDU 5 }
pduExternalSensor  	  	OBJECT IDENTIFIER       ::= { cPDU 6 }
pduSmartCabinet  	  	OBJECT IDENTIFIER       ::= { cPDU 7 }
pduTraps		  		OBJECT IDENTIFIER       ::= { cPDU 8 }
pduEhandle				OBJECT IDENTIFIER 		::= { cPDU 9 }

-- Start pduNamePlate

pduNamePlateTableSize  OBJECT-TYPE
	SYNTAX 	Integer32 (1..256)
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"The total number of PDUs"
	::= { pduNamePlate 1 }

-- pduNamePlateTable
pduNamePlateTable  OBJECT-TYPE
	SYNTAX SEQUENCE OF PduNamePlateEntry
	MAX-ACCESS  	not-accessible
	STATUS 	current
	DESCRIPTION 
		"A table of PDU nameplate data"
	::= { pduNamePlate 2 }
	
pduNamePlateEntry  OBJECT-TYPE
	SYNTAX 	PduNamePlateEntry
	MAX-ACCESS  	not-accessible
	STATUS 	current
	DESCRIPTION 
		"Nameplate data from the PDU being queried. The numbers of entries equals the value of pduNamePlateTableSize."
	INDEX { pduNamePlateIndex }
	::= { pduNamePlateTable 1 }

PduNamePlateEntry ::= SEQUENCE {
	pduNamePlateIndex
		Integer32,
	pduNamePlateName
		DisplayString,
	pduNamePlateLocation
		DisplayString,
	pduNamePlateInetAddressType
		INTEGER,
	pduNamePlateIPAddress
		InetAddress,
	pduNamePlateInetNetMask
		InetAddress,
	pduNamePlateInetGateway
		InetAddress,
	pduNamePlateMACAddress
		MacAddress,
	pduNamePlateUTCTimeOffset
		DisplayString,
	pduNamePlateModelNumber
		DisplayString,
	pduNamePlatePartNumber
		DisplayString,
	pduNamePlateSerialNumber
		DisplayString,
	pduNamePlateDateofManufacture
		DisplayString,
	pduNamePlateFirmwareVersion
		DisplayString,
	pduNamePlateFirmwareVersionTimeStamp
		DisplayString,
	pduNamePlateType
		INTEGER,
	pduNamePlateIPV6Address
		DisplayString,
	pduNamePlateHWVersion
		DisplayString
	}

pduNamePlateIndex  OBJECT-TYPE
	SYNTAX 	Integer32 (1..256)
	MAX-ACCESS  	not-accessible
	STATUS 	current
	DESCRIPTION 
		"The index of the PDU nameplate table entry"
	::= { pduNamePlateEntry 1 }
	
pduNamePlateName  OBJECT-TYPE
	SYNTAX 	DisplayString
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"A user-defined string identifying the PDU"
	::= { pduNamePlateEntry 2 }
	
pduNamePlateLocation  OBJECT-TYPE
	SYNTAX 	DisplayString
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"A user-defined string identifying the location of PDU"
	::= { pduNamePlateEntry 3 }

pduNamePlateInetAddressType  OBJECT-TYPE
	SYNTAX 	INTEGER
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"The type of address format"
	::= { pduNamePlateEntry 4 }
	
pduNamePlateIPAddress  OBJECT-TYPE
	SYNTAX 	InetAddress
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"The current IP address. A value of 0.0.0.0 indicates an error or an unset option"
	::= { pduNamePlateEntry 5 }
	
pduNamePlateInetNetMask  OBJECT-TYPE
	SYNTAX 	InetAddress
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"The current netmask. A value of 0.0.0.0 indiates an error or an unset option"
	::= { pduNamePlateEntry 6 }
	
pduNamePlateInetGateway  OBJECT-TYPE
	SYNTAX 	InetAddress
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"The current gateway. A value of 0.0.0.0 indicates an error or an unset option"
	::= { pduNamePlateEntry 7 }
	
pduNamePlateMACAddress  OBJECT-TYPE
	SYNTAX 	MacAddress
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"The assigned MAC address for the PDU"
	::= { pduNamePlateEntry 8 }
	
pduNamePlateUTCTimeOffset  OBJECT-TYPE
	SYNTAX 	DisplayString
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"The difference in hours and minutes from Coordinated Universal 
		Time(UTC) for the time used in a particular time zone"
	::= { pduNamePlateEntry 9 }
	
pduNamePlateModelNumber  OBJECT-TYPE
	SYNTAX 	DisplayString
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"The PDU model number"
	::= { pduNamePlateEntry 10 }
pduNamePlatePartNumber  OBJECT-TYPE
	SYNTAX 	DisplayString
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"The PDU part number"
	::= { pduNamePlateEntry 11 }
	
pduNamePlateSerialNumber  OBJECT-TYPE
	SYNTAX 	DisplayString
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"The PDU serial number"
	::= { pduNamePlateEntry 12 }
	
pduNamePlateDateofManufacture  OBJECT-TYPE
	SYNTAX 	DisplayString
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"The date the PDU was manufactured in mm/dd/yyyy format"
	::= { pduNamePlateEntry 13 }

pduNamePlateFirmwareVersion  OBJECT-TYPE
	SYNTAX 	DisplayString
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"The PDU firmware version"
	::= { pduNamePlateEntry 14 }
	
pduNamePlateFirmwareVersionTimeStamp  OBJECT-TYPE
	SYNTAX 	DisplayString
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"Timestamp of when the PDU firmware was last updated"
	::= { pduNamePlateEntry 15 }
	
pduNamePlateType  OBJECT-TYPE
	SYNTAX 	INTEGER {singlePhase (1),delta (2),wye (3)}
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"The type of input"
	::= { pduNamePlateEntry 16 }
	
pduNamePlateIPV6Address  OBJECT-TYPE
	SYNTAX 	DisplayString
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"The current IPV6 address. A value of 0.0.0.0 indicates an error or an unset option"
::= { pduNamePlateEntry 17 }

pduNamePlateHWVersion OBJECT-TYPE 
    SYNTAX DisplayString 
    MAX-ACCESS read-only 
    STATUS current 
    DESCRIPTION 
        "Displays Hardware version of the PDU." 
    ::= { pduNamePlateEntry 18 }
	
-- Start pduUnit

pduUnitTableSize  OBJECT-TYPE
	SYNTAX 	Integer32 (1..256)
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"The number of units."
	::= { pduUnit 1 }
	
pduUnitConfigTable  OBJECT-TYPE
	SYNTAX SEQUENCE OF PduUnitConfigEntry
	MAX-ACCESS  	not-accessible
	STATUS 	current
	DESCRIPTION 
		"A table of PDU configuration data"
	::= { pduUnit 2 }
	
pduUnitConfigEntry  OBJECT-TYPE
	SYNTAX 	PduUnitConfigEntry
	MAX-ACCESS  	not-accessible
	STATUS 	current
	DESCRIPTION 
		"Configuration data from the PDU being queried. The number of entries equals the value of pduUnitTableSize"
	INDEX { pduUnitConfigIndex }
	::= { pduUnitConfigTable 1 }

PduUnitConfigEntry ::= SEQUENCE {
	pduUnitConfigIndex
		Integer32,
	pduUnitConfigName
		DisplayString,
	pduUnitConfigLocation
		DisplayString,
	pduUnitConfigDisplayOrientation
		INTEGER,
	pduUnitConfigOledDisplayControl
		INTEGER,
	pduUnitConfigColdstartDelay
		Unsigned32,
	pduUnitConfigGlobalOutletStateOnStartup
		INTEGER,
	pduUnitConfigLowerCriticalThreshold
		Unsigned32,
	pduUnitConfigLowerWarningThreshold
		Unsigned32,
	pduUnitConfigUpperCriticalThreshold
		Unsigned32,
	pduUnitConfigUpperWarningThreshold
		Unsigned32,
	pduUnitConfigAlarmResetThreshold
		Unsigned32,
	pduUnitConfigAlarmStateChangeDelay
		Unsigned32,
	pduUnitConfigEnabledThresholds
		BITS,
	pduUnitConfigPeakPowerReset
		INTEGER,
	pduUnitConfigEnergyReset
		INTEGER,
	pduUnitConfigOutletPeakPowerReset
		INTEGER,
	pduUnitConfigOutletEnergyReset
		INTEGER,
	pduUnitConfigSsh
		INTEGER,
	pduUnitConfigResetNetworkManagementCard
		INTEGER,
	pduUnitConfigUsb
		INTEGER,
	pduUnitConfigDaisyChainState
		INTEGER,
	pduUnitConfigTelnet
		INTEGER	
	}

pduUnitConfigIndex  OBJECT-TYPE
	SYNTAX 	Integer32 (1..256)
	MAX-ACCESS  	not-accessible
	STATUS 	current
	DESCRIPTION 
		"The index of the PDU Unit Config Entry"
	::= { pduUnitConfigEntry 1 }
	
pduUnitConfigName  OBJECT-TYPE
	SYNTAX 	DisplayString
	MAX-ACCESS  	read-write
	STATUS 	current
	DESCRIPTION 
		"A user-defined string identifying the PDU"
	::= { pduUnitConfigEntry 2 }
	
pduUnitConfigLocation  OBJECT-TYPE
	SYNTAX 	DisplayString
	MAX-ACCESS  	read-write
	STATUS 	current
	DESCRIPTION 
		"A user-defined string identifying the location of the PDU"
	::= { pduUnitConfigEntry 3 }
	
pduUnitConfigDisplayOrientation  OBJECT-TYPE
	SYNTAX 	INTEGER {
		displayNormal (1),
		displayReverse (2)
	}
	MAX-ACCESS  	read-write
	STATUS 	current
	DESCRIPTION 
		"Indicates the intended physical orientation of the oLED display
		displayNormal (1) indicates normal orientation. 
		displayReverse (2) indicates upside down orientation
		NOTE:
		This OID is compatible only with the two display NMC module.  It does not work with the single display NMC module."
	::= { pduUnitConfigEntry 4 }

pduUnitConfigOledDisplayControl  OBJECT-TYPE
	SYNTAX 	INTEGER {
		displayOff (1),
		displayOn (2)
	}
	MAX-ACCESS  	read-write
	STATUS 	current
	DESCRIPTION 
		"Used to turn oled display On or Off
		displayOff (1) to turn dispaly OFF. 
		displayOn (2) to turn dispaly ON"
	::= { pduUnitConfigEntry 5 }
	
pduUnitConfigColdstartDelay  OBJECT-TYPE
	SYNTAX 	Unsigned32 (0..3600)
	MAX-ACCESS  	read-write
	STATUS 	current
	DESCRIPTION 
		"The amount of time, specified in seconds, between when power 
		is provided to the PDU and when the PDU start providing basic master
		power to the outlets"
	::= { pduUnitConfigEntry 6 }
	
pduUnitConfigGlobalOutletStateOnStartup  OBJECT-TYPE
	SYNTAX 	INTEGER {
		off (0),
		on (1),
		lastKnownState (2)
	}
	MAX-ACCESS  	read-write
	STATUS 	current
	DESCRIPTION 
		"The outlet state on device startup; applies to all outlets 
		unless overridden at the outlet level"
	::= { pduUnitConfigEntry 7 }
	
pduUnitConfigLowerCriticalThreshold  OBJECT-TYPE
	SYNTAX 	Unsigned32
	MAX-ACCESS  	read-write
	STATUS 	current
	DESCRIPTION 
		"User-defined lower critical unit active power alarm threshold measured in Watts"
	::= { pduUnitConfigEntry 8 }
	
pduUnitConfigLowerWarningThreshold  OBJECT-TYPE
	SYNTAX 	Unsigned32
	MAX-ACCESS  	read-write
	STATUS 	current
	DESCRIPTION 
		"User-defined lower non-critical (warning) unit active power alarm threshold measured in Watts"
	::= { pduUnitConfigEntry 9 }
	
pduUnitConfigUpperCriticalThreshold  OBJECT-TYPE
	SYNTAX 	Unsigned32
	MAX-ACCESS  	read-write
	STATUS 	current
	DESCRIPTION 
		"User-defined upper critical unit active power alarm threshold measured in Watts"
	::= { pduUnitConfigEntry 10 }
	
pduUnitConfigUpperWarningThreshold  OBJECT-TYPE
	SYNTAX 	Unsigned32
	MAX-ACCESS  	read-write
	STATUS 	current
	DESCRIPTION 
		"User-defined upper non-critical (warning) unit active power alarm threshold measured in Watts"
	::= { pduUnitConfigEntry 11 }
	
pduUnitConfigAlarmResetThreshold  OBJECT-TYPE
	SYNTAX 	Unsigned32
	MAX-ACCESS  	read-write
	STATUS 	current
	DESCRIPTION 
		"The hysteresis used for deassertions in Watts"
	::= { pduUnitConfigEntry 12 }
	
pduUnitConfigAlarmStateChangeDelay  OBJECT-TYPE
	SYNTAX 	Unsigned32
	MAX-ACCESS  	read-write
	STATUS 	current
	DESCRIPTION 
		"The delay measured in samples before a state is asserted. If the value is zero, then the state is asserted as soon as it is detected; if it is non-zero, say n, then the assertion condition must exist for n+1 consecutive samples before the corresponding assertion event is reported."
	::= { pduUnitConfigEntry 13 }
	
pduUnitConfigEnabledThresholds  OBJECT-TYPE
	SYNTAX 	BITS {
		lowerCritical (0),
		lowerWarning (1),
		upperWarning  (2),
		upperCritical (3)
	}
	MAX-ACCESS  	read-write
	STATUS 	current
	DESCRIPTION 
		"A bit string indicating which alarm thresholds are enabled"
	::= { pduUnitConfigEntry 14 }
	
pduUnitConfigPeakPowerReset  OBJECT-TYPE
	SYNTAX 	INTEGER {
		noOperation (1),
		reset (2)
	}
	MAX-ACCESS  	read-write
	STATUS 	current
	DESCRIPTION 
		"Setting this OID to reset (2) will cause the existing peak power value 
		to be replaced by the current load power value. Getting this OID will 
		do nothing and return the noOperation(1) value. "
	::= { pduUnitConfigEntry 15 }
	
pduUnitConfigEnergyReset  OBJECT-TYPE
	SYNTAX 	INTEGER {
		noOperation (1),
		reset (2),
		notSupported (3)
	}
	MAX-ACCESS  	read-write
	STATUS 	current
	DESCRIPTION 
		"Setting this OID to reset (2) will cause the device energy meter value 
		to be reset to zero. Getting this OID in models that support this 
		feature will do nothing and return the noOperation(1) value. Models 
		that do not support this feature will respond to this OID with a 
		value of notSupported (3). Attempts to set this OID in these models will fail. "
	::= { pduUnitConfigEntry 16 }

pduUnitConfigOutletPeakPowerReset  OBJECT-TYPE
	SYNTAX 	INTEGER {
		noOperation (1),
		reset (2),
		notSupported (3)
	}
	MAX-ACCESS  	read-write
	STATUS 	current
	DESCRIPTION 
		"Setting this OID to reset (2) will cause the outlet peak power meter value 
		to be reset to zero. Getting this OID in models that support this 
		feature will do nothing and return the noOperation(1) value. Models 
		that do not support this feature will respond to this OID with a 
		value of notSupported (3). Attempts to set this OID in these models will fail. "
	::= { pduUnitConfigEntry 17 }

pduUnitConfigOutletEnergyReset  OBJECT-TYPE
	SYNTAX 	INTEGER {
		noOperation (1),
		reset (2),
		notSupported (3)
	}
	MAX-ACCESS  	read-write
	STATUS 	current
	DESCRIPTION 
		"Setting this OID to reset (2) will cause the outlet energy meter value 
		to be reset to zero. Getting this OID in models that support this 
		feature will do nothing and return the noOperation(1) value. Models 
		that do not support this feature will respond to this OID with a 
		value of notSupported (3). Attempts to set this OID in these models will fail. "
	::= { pduUnitConfigEntry 18 }

pduUnitConfigSsh  OBJECT-TYPE
	SYNTAX 	INTEGER {
		off (0),
		on (1)
	}
	MAX-ACCESS  	read-write
	STATUS 	current
	DESCRIPTION 
		"Setting this OID to off(0) will disable the SSH connection.  Setting this OID to on(1) will enable the SSH connection."
	::= { pduUnitConfigEntry 19 }
	
pduUnitConfigResetNetworkManagementCard  OBJECT-TYPE
	SYNTAX 	INTEGER {
		noOperation (0),
		reset (1)
	}
	MAX-ACCESS  	read-write
	STATUS 	current
	DESCRIPTION 
		"Getting this OID will return noOperation(0). Setting this OID to reset(1) will reset NMC."
	::= { pduUnitConfigEntry 20 }
	
pduUnitConfigUsb  OBJECT-TYPE
	SYNTAX 	INTEGER {
		off (0),
		on (1)
	}
	MAX-ACCESS  	read-write
	STATUS 	current
	DESCRIPTION 
		"Setting this OID to off(0) will disable the USB port.  Setting this OID to on(1) will enable the USB port."
	::= { pduUnitConfigEntry 21 }
	
pduUnitConfigDaisyChainState	OBJECT-TYPE
	SYNTAX 	INTEGER {
		daisychainqna (0),
		daisychainrna (1)
	}
	MAX-ACCESS  	read-write
	STATUS 	current
	DESCRIPTION 
		"Setting this OID to 0 will enable daisychain qna mode.
		 Setting this OID to 1 will enable daisychain rna mode. Should be applied on last pdu in DaisyChain"
	::= { pduUnitConfigEntry 22 }
	 
pduUnitConfigTelnet  OBJECT-TYPE
	SYNTAX 	INTEGER {
		off (0),
		on (1)
	}
	MAX-ACCESS  	read-write
	STATUS 	current
	DESCRIPTION 
		"Setting this OID to off(0) will disable the Telnet connection.  Setting this OID to on(1) will enable the Telnet connection.
		 Changes made will take effect only after reboot."
	::= { pduUnitConfigEntry 23 }
	
pduUnitPropertiesTable  OBJECT-TYPE
	SYNTAX SEQUENCE OF PduUnitPropertiesEntry
	MAX-ACCESS  	not-accessible
	STATUS 	current
	DESCRIPTION 
		"A table of PDU properties"
	::= { pduUnit 3 }
	
pduUnitPropertiesEntry  OBJECT-TYPE
	SYNTAX 	PduUnitPropertiesEntry
	MAX-ACCESS  	not-accessible
	STATUS 	current
	DESCRIPTION 
		"A unit properties entry containing objects for a particular unit."
	INDEX { pduUnitPropertiesIndex }
	::= { pduUnitPropertiesTable 1 }

PduUnitPropertiesEntry ::= SEQUENCE {
	pduUnitPropertiesIndex
		Integer32,
	pduUnitPropertiesName
		DisplayString,
	pduUnitPropertiesOutletCount
		Integer32,
	pduUnitPropertiesSwitchedOutletCount
		Integer32,
	pduUnitPropertiesMeteredOutletCount
		Integer32,
	pduUnitPropertiesInputPhaseCount
		Integer32,
	pduUnitPropertiesCircuitBreakerCount
		Integer32,
	pduUnitPropertiesMaxExternalSensorCount
		Integer32,
	pduUnitPropertiesConnExternalSensorCount
		Integer32,
	pduUnitPropertiesRatedVoltage
		DisplayString,
	pduUnitPropertiesRatedMaxCurrent
		DisplayString,
	pduUnitPropertiesRatedFrequency
		DisplayString,
	pduUnitPropertiesRatedPower
		DisplayString,
	pduUnitPropertiesOrientation
		INTEGER,
	pduUnitPropertiesOutletLayout
		INTEGER,
	pduUnitPropertiesCascadeMemberType
		INTEGER
	}

pduUnitPropertiesIndex  OBJECT-TYPE
	SYNTAX 	Integer32 (1..256)
	MAX-ACCESS  	not-accessible
	STATUS 	current
	DESCRIPTION 
		"The index of the PDU properties table entry"
	::= { pduUnitPropertiesEntry 1 }
	
pduUnitPropertiesName  OBJECT-TYPE
	SYNTAX 	DisplayString
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"A user-defined string identifying the PDU"
	::= { pduUnitPropertiesEntry 2 }
	
pduUnitPropertiesOutletCount  OBJECT-TYPE
	SYNTAX 	Integer32 (1..256)
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"The total number of outlets on the PDU"
	::= { pduUnitPropertiesEntry 3 }
	
pduUnitPropertiesSwitchedOutletCount  OBJECT-TYPE
	SYNTAX 	Integer32 (1..256)
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"The total number of switched outlets on the PDU"
	::= { pduUnitPropertiesEntry 4 }
	
pduUnitPropertiesMeteredOutletCount  OBJECT-TYPE
	SYNTAX 	Integer32 (1..256)
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"The total number of metered outlets on the PDU"
	::= { pduUnitPropertiesEntry 5 }
	
pduUnitPropertiesInputPhaseCount  OBJECT-TYPE
	SYNTAX 	Integer32 (1..256)
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"The total number of phases on the PDU"
	::= { pduUnitPropertiesEntry 6 }

pduUnitPropertiesCircuitBreakerCount  OBJECT-TYPE
	SYNTAX 	Integer32 (0..255)
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"The total number of circuit breaker on the PDU"
	::= { pduUnitPropertiesEntry 7 }
	
pduUnitPropertiesMaxExternalSensorCount  OBJECT-TYPE
	SYNTAX 	Integer32 (0..255)
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"The maximum number of external sensors that can be connected to the PDU"
	::= { pduUnitPropertiesEntry 8 }
	
pduUnitPropertiesConnExternalSensorCount  OBJECT-TYPE
	SYNTAX 	Integer32 (0..255)
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"The current number of external sensors connected to the PDU"
	::= { pduUnitPropertiesEntry 9 }
	
pduUnitPropertiesRatedVoltage  OBJECT-TYPE
	SYNTAX 	DisplayString
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"The PDU voltage rating in Volts"
	::= { pduUnitPropertiesEntry 10 }
	
pduUnitPropertiesRatedMaxCurrent  OBJECT-TYPE
	SYNTAX 	DisplayString
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"The PDU current rating in Amps"
	::= { pduUnitPropertiesEntry 11 }
	
pduUnitPropertiesRatedFrequency  OBJECT-TYPE
	SYNTAX 	DisplayString
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"The PDU frequency rating in Hz"
	::= { pduUnitPropertiesEntry 12 }
	
pduUnitPropertiesRatedPower  OBJECT-TYPE
	SYNTAX 	DisplayString
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"The PDU VA (VoltAmps) rating."
	::= { pduUnitPropertiesEntry 13 }
	
pduUnitPropertiesOrientation  OBJECT-TYPE
	SYNTAX 	INTEGER {
		horizontal (1),
		vertical (2)
	}
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"The PDU orientation "
	::= { pduUnitPropertiesEntry 14 }
	
pduUnitPropertiesOutletLayout  OBJECT-TYPE
	SYNTAX 	INTEGER {
		seqPhaseToNuetral (1),
		seqPhaseToPhase (2),
		seqPhToNeu21PhToPh (3),
		seqPhToPhGrouped (4),
		seqPhToNGrouped (5),
		seqPToN1516PToPGrouped (6),
		seqPhToPh2xGrouped (7),
		seqPhToN2xGrouped (8),
		seqNotApplicable (9)
	}
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"The outlet layout for the PDU. Getting this OID will return outlet layout for the device.
		seqPhaseToNeutral(1) indicates outlet layout as follows:
		1:1-N,2:2-N,3:3-N,4:1-N,5:2-N,...
		seqPhaseToPhase(2) indicates outlet layout as follows:
		1:1-2,2:2-3,3:3-1,4:1-2,5:2-3,...
		seqPhToNeu21PhToPh(3) indicates outlet layout as follows:
		1:1-N,2:2-N...21:3-N,22:1-2,23:2-3,24:3-1,...
		seqPhToPhGrouped(4) indicates outlet layout as follows:
		This unit has 3 outlet groups.  Group 1:1-2, Group 2:2-3, Group 3:3-1.
		seqPhToNGrouped(5) indicates outlet layout as follows:
		This unit has 3 outlet groups.  Group 1:1-N, Group 2:2-N, Group 3:3-N.
		seqPToN1516PToPGrouped(6) indicates outlet layout as follows:
		This unit has 4 outlet groups. Group 1 (Outlets 1-14):1-2,
		Group 2 (Outlets 15-16):1-N, Group 3:2-3, Group 4:3-1.
		seqPhToPh2xGrouped(7) indicates outlet layout as follows:
		This unit has 6 outlet groups.  Group 1:1-2, Group 2:1-2, Group 3:2-3,
		Group 4:2-3, Group 5:3-1, Group 6:3-1.
		seqPhToN2xGrouped(8) indicates outlet layout as follows:
		This unit has 6 outlet groups.  Group 1:1-N, Group 2:1-N, Group 3:2-N,
		Group 4:2-N, Group 5:3-N, Group 6:3-N.
		seqNotApplicable(9):"
	::= { pduUnitPropertiesEntry 15 }
	
pduUnitPropertiesCascadeMemberType  OBJECT-TYPE
	SYNTAX 	INTEGER {
		standalone (1),
		parent (2),
		child (3)
	}
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"The cascading member type"
	::= { pduUnitPropertiesEntry 16 }
		
pduUnitStatusTable  OBJECT-TYPE
	SYNTAX SEQUENCE OF PduUnitStatusEntry
	MAX-ACCESS  	not-accessible
	STATUS 	current
	DESCRIPTION 
		"A table of PDU status information"
	::= { pduUnit 4 }
	
pduUnitStatusEntry  OBJECT-TYPE
	SYNTAX 	PduUnitStatusEntry
	MAX-ACCESS  	not-accessible
	STATUS 	current
	DESCRIPTION 
		"Status information from the PDU being queried"
	INDEX { pduUnitStatusIndex }
	::= { pduUnitStatusTable 1 }

PduUnitStatusEntry ::= SEQUENCE {
	pduUnitStatusIndex
		Integer32,
	pduUnitStatusName
		DisplayString,
	pduUnitStatusLoadState
		INTEGER,
	pduUnitStatusActivePower
		Integer32,
	pduUnitStatusApparentPower
		Integer32,
	pduUnitStatusPeakPower
		Integer32,
	pduUnitStatusPeakPowerTimestamp
		DisplayString,
	pduUnitStatusPeakPowerStartTime
		DisplayString,
	pduUnitStatusEnergy
		Integer32,
	pduUnitStatusResettableEnergy
		Integer32,
	pduUnitStatusEnergyStartTime
		DisplayString,
	pduUnitStatusOutletsEnergyStartTime
		DisplayString,
	pduUnitStatusPowerFactor
		Integer32
	}

pduUnitStatusIndex  OBJECT-TYPE
	SYNTAX 	Integer32 (1..256)
	MAX-ACCESS  	not-accessible
	STATUS 	current
	DESCRIPTION 
		"The index of the PDU status table entry"
	::= { pduUnitStatusEntry 1 }
	
pduUnitStatusName  OBJECT-TYPE
	SYNTAX 	DisplayString
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"A user-defined string identifying the PDU"
	::= { pduUnitStatusEntry 2 }
	
pduUnitStatusLoadState  OBJECT-TYPE
	SYNTAX 	INTEGER {
		upperCritical (1),
		upperWarning (2),
		lowerWarning (3),
		lowerCritical (4),
		normal (5)
	}
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"Returns the present load status of the PDU based on Active Power."
	::= { pduUnitStatusEntry 3 }
	
pduUnitStatusActivePower  OBJECT-TYPE
	SYNTAX 	Integer32
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"Returns power consumption, in Watts(W), 
		of the PDU being queried."
	::= { pduUnitStatusEntry 4 }

pduUnitStatusApparentPower  OBJECT-TYPE
	SYNTAX 	Integer32
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"Returns power consumption, in Volt-Amps(VA) 
		of the PDU load being queried."
	::= { pduUnitStatusEntry 5 }
	
pduUnitStatusPeakPower  OBJECT-TYPE
	SYNTAX 	Integer32
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"Returns peak power consumption, in Watts(W), 
		of the PDU being queried."
	::= { pduUnitStatusEntry 6 }
	
pduUnitStatusPeakPowerTimestamp  OBJECT-TYPE
	SYNTAX 	DisplayString
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"Indicates the date and time that peak power consumption occurred"
	::= { pduUnitStatusEntry 7 }
	
pduUnitStatusPeakPowerStartTime  OBJECT-TYPE
	SYNTAX 	DisplayString
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"Indicates the date and time of the last device peak power reset"
	::= { pduUnitStatusEntry 8 }
	
pduUnitStatusEnergy  OBJECT-TYPE
	SYNTAX 	Integer32
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"Returns total energy consumed, in tenths of Kilowatt-Hours(kWh), of the PDU over its lifetime."		
	::= { pduUnitStatusEntry 9 }

pduUnitStatusResettableEnergy  OBJECT-TYPE
	SYNTAX 	Integer32
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"A user resettable energy meter measuring PDU energy consumption 
		in tenths of kilowatt-hours(kWh)."
	::= { pduUnitStatusEntry 10 }
	
pduUnitStatusEnergyStartTime  OBJECT-TYPE
	SYNTAX 	DisplayString
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"Indicates the date and time of the last device energy meter reset"
	::= { pduUnitStatusEntry 11 }
	
pduUnitStatusOutletsEnergyStartTime  OBJECT-TYPE
	SYNTAX 	DisplayString
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"Indicates the date and time of the last outlets energy meter reset"
	::= { pduUnitStatusEntry 12 }

pduUnitStatusPowerFactor  OBJECT-TYPE
	SYNTAX 	Integer32
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"Returns the ratio of active to apparent power of the PDU, in the hundreths of PowerFactor."
	::= { pduUnitStatusEntry 13 }

-- Power share table


pduUnitPsTable  OBJECT-TYPE
	SYNTAX SEQUENCE OF PduUnitPsEntry
	MAX-ACCESS  	not-accessible
	STATUS 	current
	DESCRIPTION 
		"Aggregate Object with number of entries equal to number of PDUs and Power share "
	::= { pduUnit 5}
	
pduUnitPsEntry  OBJECT-TYPE
	SYNTAX 	PduUnitPsEntry
	MAX-ACCESS  	not-accessible
	STATUS 	current
	DESCRIPTION 
		"The Power share entry containing the avaliable, input, output etc."
	INDEX { pduUnitPsIndex }
	::= { pduUnitPsTable 1 }


PduUnitPsEntry ::= SEQUENCE {
		pduUnitPsIndex
			INTEGER,
		pduUnitPsSupportUpstreamStatus
			INTEGER,
		pduUnitPsSupportDownstreamStatus		
			INTEGER,	
		pduUnitPsOptMode
			INTEGER
		pduUnitPsFunc
			INTEGER,
		pduUnitPsBackupProtection
			INTEGER,
		pduUnitPsOutput
			INTEGER
	 }

pduUnitPsIndex OBJECT-TYPE
	SYNTAX INTEGER (1..4)
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION
		"The index of the PDU Power share table entry"
	::= { pduUnitPsEntry 1 }


pduUnitPsSupportUpstreamStatus OBJECT-TYPE
	SYNTAX INTEGER
		{
		notAvailable(0),
		available(1)
		}
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION
		"Deprecated because of newly added OID"
	::= { pduUnitPsEntry 2}		
	
pduUnitPsSupportDownstreamStatus OBJECT-TYPE
	SYNTAX INTEGER
		{
		notAvailable(0),
		available(1)
		}
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION
		"Deprecated because of newly added OID"
	::= { pduUnitPsEntry 3 }	

pduUnitPsOptMode OBJECT-TYPE
	SYNTAX INTEGER
		{
		backupPower(0),
		mainPower(1)
		}
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION
		"Operating power status. "
	::= { pduUnitPsEntry 4 }
	
pduUnitPsFunc OBJECT-TYPE
	SYNTAX INTEGER
		{
		off(0),
		on(1)
		}
	MAX-ACCESS	read-write
	STATUS	current
	DESCRIPTION
		"Setting this OID to off(0) will disable the Powershare function.
		 Setting this OID to on(1) will enable the Powershare function."
	::= {pduUnitPsEntry 5 }
	
pduUnitPsBackupProtection OBJECT-TYPE
	SYNTAX INTEGER
		{
		notAvailable(0),
		available(1)
		}
		MAX-ACCESS read-only
		STATUS current
		DESCRIPTION
			"Power share support from either of the adjacent PDUs "
		::= { pduUnitPsEntry 6}		
			
pduUnitPsOutput OBJECT-TYPE
	SYNTAX INTEGER
		{
		notAvailable(0),
		available(1)
		}
		MAX-ACCESS read-only
		STATUS current
		DESCRIPTION
			"Power share support to either of the adjacent PDUs "
		::= { pduUnitPsEntry 7}

-- Start pduInputPhase
pduInputPhaseTableSize  OBJECT-TYPE
	SYNTAX 	Integer32 (1..256)
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"The number of PDU Input Phases "
	::= { pduInputPhase 1 }
	
pduInputPhaseConfigTable  OBJECT-TYPE
	SYNTAX SEQUENCE OF PduInputPhaseConfigEntry
	MAX-ACCESS  	not-accessible
	STATUS 	current
	DESCRIPTION 
		"A table of PDU Input Phase configuration data"
	::= { pduInputPhase 2 }
	
pduInputPhaseConfigEntry  OBJECT-TYPE
	SYNTAX 	PduInputPhaseConfigEntry
	MAX-ACCESS  	not-accessible
	STATUS 	current
	DESCRIPTION 
		"An input phase entry containing objects for a particular input phase."
	INDEX { pduUnitConfigIndex, pduInputPhaseConfigIndex }
	::= { pduInputPhaseConfigTable 1 }

PduInputPhaseConfigEntry ::= SEQUENCE {
	pduInputPhaseConfigIndex
		Integer32,
	pduInputPhaseConfigCount
		Integer32,
	pduInputPhaseConfigOverloadRestriction
		INTEGER,
	pduInputPhaseConfigCurrentLowerCriticalThreshold
		Unsigned32,
	pduInputPhaseConfigCurrentLowerWarningThreshold
		Unsigned32,
	pduInputPhaseConfigCurrentUpperCriticalThreshold
		Unsigned32,
	pduInputPhaseConfigCurrentUpperWarningThreshold
		Unsigned32,
	pduInputPhaseConfigVoltageLowerCriticalThreshold
		Unsigned32,
	pduInputPhaseConfigVoltageLowerWarningThreshold
		Unsigned32,
	pduInputPhaseConfigVoltageUpperCriticalThreshold
		Unsigned32,
	pduInputPhaseConfigVoltageUpperWarningThreshold
		Unsigned32,
	pduInputPhaseConfigCurrentAlarmResetThreshold
		Unsigned32,
	pduInputPhaseConfigCurrentAlarmStateChangeDelay
		Integer32,
	pduInputPhaseConfigCurrentEnabledThresholds
		BITS,
	pduInputPhaseConfigVoltageAlarmResetThreshold
		Unsigned32,
	pduInputPhaseConfigVoltageAlarmStateChangeDelay
		Integer32,
	pduInputPhaseConfigVoltageEnabledThresholds
		BITS,
	pduInputPhaseConfigLineVoltageLowerCriticalThreshold
		Unsigned32,
	pduInputPhaseConfigLineVoltageLowerWarningThreshold
		Unsigned32,
	pduInputPhaseConfigLineVoltageUpperCriticalThreshold
		Unsigned32,
	pduInputPhaseConfigLineVoltageUpperWarningThreshold
		Unsigned32,
	pduInputPhaseConfigLineVoltageAlarmResetThreshold
		Unsigned32,
	pduInputPhaseConfigLineVoltageAlarmStateChangeDelay
		Integer32,
	pduInputPhaseConfigLineVoltageEnabledThresholds
		BITS
	}

pduInputPhaseConfigIndex  OBJECT-TYPE
	SYNTAX 	Integer32 (1..256)
	MAX-ACCESS  	not-accessible
	STATUS 	current
	DESCRIPTION 
		"The index of the PDU Input Phase configuration table entry"
	::= { pduInputPhaseConfigEntry 1 }
	
pduInputPhaseConfigCount  OBJECT-TYPE
	SYNTAX 	Integer32 (1..256)
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"The total number of Input Phases"
	::= { pduInputPhaseConfigEntry 2 }
	
pduInputPhaseConfigOverloadRestriction  OBJECT-TYPE
	SYNTAX 	INTEGER {
		alwaysAllowTurnOn (1),
		restrictOnUpperWarning (2),
		restrictOnUpperCritical (3),
		notSupported (4)
	}
	MAX-ACCESS  	read-write
	STATUS 	current
	DESCRIPTION 
		"This OID controls the behavior of a Switched PDU Input Phase when an 
		overload condition is possible and additional outlets are requested 
		to be turned on. Setting this OID to alwaysAllowTurnON (1) will always 
		allow the outlets on the corresponding Input Phase to turn on. Setting 
		this OID to restrictOnUpperWarning (2) will not allow outlets on the 
		corresponding Input Phase to turn on if the 
		pduInputPhaseConfigUpperWarningThreshold OID is exceeded. Setting 
		this OID to restrictOnUpperCritical (3) will not allow outlets on 
		the corresponding Input Phase to turn on if the 
		pduInputPhaseConfigUpperCriticalThreshold OID is exceeded. Models 
		that do not support this feature will respond to this OID with a 
		value of notSupported (4). Attempts to set this OID in these 
		models will fail. "
	::= { pduInputPhaseConfigEntry 3 }
	
pduInputPhaseConfigCurrentLowerCriticalThreshold  OBJECT-TYPE
	SYNTAX 	Unsigned32
	MAX-ACCESS  	read-write
	STATUS 	current
	DESCRIPTION 
		"User-defined lower critical input phase current alarm threshold in hundredths of Amps(A)."
	::= { pduInputPhaseConfigEntry 4 }
	
pduInputPhaseConfigCurrentLowerWarningThreshold  OBJECT-TYPE
	SYNTAX 	Unsigned32
	MAX-ACCESS  	read-write
	STATUS 	current
	DESCRIPTION 
		"User-defined lower non-critical (warning) input phase current alarm threshold in hundredths of Amps(A)."
	::= { pduInputPhaseConfigEntry 5 }
	
pduInputPhaseConfigCurrentUpperCriticalThreshold  OBJECT-TYPE
	SYNTAX 	Unsigned32
	MAX-ACCESS  	read-write
	STATUS 	current
	DESCRIPTION 
		"User-defined upper critical input phase current alarm threshold in hundredths of Amps(A)."
	::= { pduInputPhaseConfigEntry 6 }
	
pduInputPhaseConfigCurrentUpperWarningThreshold  OBJECT-TYPE
	SYNTAX 	Unsigned32
	MAX-ACCESS  	read-write
	STATUS 	current
	DESCRIPTION 
		"User-defined upper non-critical (warning) input phase current alarm threshold in hundredths of Amps(A)."
	::= { pduInputPhaseConfigEntry 7 }

pduInputPhaseConfigVoltageLowerCriticalThreshold  OBJECT-TYPE
	SYNTAX 	Unsigned32
	MAX-ACCESS  	read-write
	STATUS 	current
	DESCRIPTION 
		"User-defined lower critical input phase voltage alarm threshold in Volts(V)."
	::= { pduInputPhaseConfigEntry 8 }
	
pduInputPhaseConfigVoltageLowerWarningThreshold  OBJECT-TYPE
	SYNTAX 	Unsigned32
	MAX-ACCESS  	read-write
	STATUS 	current
	DESCRIPTION 
		"User-defined lower non-critical (warning) input phase voltage alarm threshold in Volts(V)."
	::= { pduInputPhaseConfigEntry 9 }
	
pduInputPhaseConfigVoltageUpperCriticalThreshold  OBJECT-TYPE
	SYNTAX 	Unsigned32
	MAX-ACCESS  	read-write
	STATUS 	current
	DESCRIPTION 
		"User-defined upper critical input phase voltage alarm threshold in Volts(V)."
	::= { pduInputPhaseConfigEntry 10 }
	
pduInputPhaseConfigVoltageUpperWarningThreshold  OBJECT-TYPE
	SYNTAX 	Unsigned32
	MAX-ACCESS  	read-write
	STATUS 	current
	DESCRIPTION 
		"User-defined upper non-critical (warning) input phase voltage alarm threshold in Volts(V)."
	::= { pduInputPhaseConfigEntry 11 }
	
pduInputPhaseConfigCurrentAlarmResetThreshold  OBJECT-TYPE
	SYNTAX 	Unsigned32
	MAX-ACCESS  	read-write
	STATUS 	current
	DESCRIPTION 
		"The hysteresis used for current alarm deassertions in hundredths of Amps(A)."
	::= { pduInputPhaseConfigEntry 12 }
	
pduInputPhaseConfigCurrentAlarmStateChangeDelay  OBJECT-TYPE
	SYNTAX 	Integer32
	MAX-ACCESS  	read-write
	STATUS 	current
	DESCRIPTION 
		"The delay measured in samples before a current state is asserted. If the 
		value is zero, then the state is asserted as soon as it is 
		detected; if it is non-zero, say n, then the assertion condition 
		must exist for n+1 consecutive samples before the corresponding 
		assertion event is reported. "
	::= { pduInputPhaseConfigEntry 13 }
	
pduInputPhaseConfigCurrentEnabledThresholds  OBJECT-TYPE
	SYNTAX 	BITS {
		lowerCritical (0),
		lowerWarning (1),
		upperWarning (2),
		upperCritical (3)
	}
	MAX-ACCESS  	read-write
	STATUS 	current
	DESCRIPTION 
		"A bit string indicating which current alarm thresholds are enabled."
	::= { pduInputPhaseConfigEntry 14 }
	
pduInputPhaseConfigVoltageAlarmResetThreshold  OBJECT-TYPE
	SYNTAX 	Unsigned32
	MAX-ACCESS  	read-write
	STATUS 	current
	DESCRIPTION 
		"The hysteresis used for voltage alarm deassertions in Volts(V)."
	::= { pduInputPhaseConfigEntry 15 }
	
pduInputPhaseConfigVoltageAlarmStateChangeDelay  OBJECT-TYPE
	SYNTAX 	Integer32
	MAX-ACCESS  	read-write
	STATUS 	current
	DESCRIPTION 
		"The delay measured in samples before a voltage state is asserted. If the 
		value is zero, then the state is asserted as soon as it is 
		detected; if it is non-zero, say n, then the assertion condition 
		must exist for n+1 consecutive samples before the corresponding 
		assertion event is reported. "
	::= { pduInputPhaseConfigEntry 16 }
	
pduInputPhaseConfigVoltageEnabledThresholds  OBJECT-TYPE
	SYNTAX 	BITS {
		lowerCritical (0),
		lowerWarning (1),
		upperWarning (2),
		upperCritical (3)
	}
	MAX-ACCESS  	read-write
	STATUS 	current
	DESCRIPTION 
		"A bit string indicating which voltage alarm thresholds are enabled."
	::= { pduInputPhaseConfigEntry 17 }
	
pduInputPhaseConfigLineVoltageLowerCriticalThreshold  OBJECT-TYPE
	SYNTAX 	Unsigned32
	MAX-ACCESS  	read-write
	STATUS 	current
	DESCRIPTION 
		"User-defined lower critical line voltage alarm threshold in Volts(V). Supported only on PDU Phase in case of Y connection."
	::= { pduInputPhaseConfigEntry 18 }
	
pduInputPhaseConfigLineVoltageLowerWarningThreshold  OBJECT-TYPE
	SYNTAX 	Unsigned32
	MAX-ACCESS  	read-write
	STATUS 	current
	DESCRIPTION 
		"User-defined lower non-critical (warning) line voltage alarm threshold in Volts(V). Supported only on PDU Phase in case of Y connection."
	::= { pduInputPhaseConfigEntry 19 }
	
pduInputPhaseConfigLineVoltageUpperCriticalThreshold  OBJECT-TYPE
	SYNTAX 	Unsigned32
	MAX-ACCESS  	read-write
	STATUS 	current
	DESCRIPTION 
		"User-defined upper critical line voltage alarm threshold in Volts(V). Supported only on PDU Phase in case of Y connection."
	::= { pduInputPhaseConfigEntry 20 }
	
pduInputPhaseConfigLineVoltageUpperWarningThreshold  OBJECT-TYPE
	SYNTAX 	Unsigned32
	MAX-ACCESS  	read-write
	STATUS 	current
	DESCRIPTION 
		"User-defined upper non-critical (warning) line voltage alarm threshold in Volts(V). Supported only on PDU Phase in case of Y connection."
	::= { pduInputPhaseConfigEntry 21 }
	
pduInputPhaseConfigLineVoltageAlarmResetThreshold  OBJECT-TYPE
	SYNTAX 	Unsigned32
	MAX-ACCESS  	read-write
	STATUS 	current
	DESCRIPTION 
		"The hysteresis used for line voltage alarm deassertions in Volts(V). Supported only on PDU Phase in case of Y connection."
	::= { pduInputPhaseConfigEntry 22 }
	
pduInputPhaseConfigLineVoltageAlarmStateChangeDelay  OBJECT-TYPE
	SYNTAX 	Integer32
	MAX-ACCESS  	read-write
	STATUS 	current
	DESCRIPTION 
		"The delay measured in samples before a line voltage state is asserted. If the 
		value is zero, then the state is asserted as soon as it is 
		detected; if it is non-zero, say n, then the assertion condition 
		must exist for n+1 consecutive samples before the corresponding 
		assertion event is reported. Supported only on PDU Phase in case of Y connection."
	::= { pduInputPhaseConfigEntry 23 }
	
pduInputPhaseConfigLineVoltageEnabledThresholds  OBJECT-TYPE
	SYNTAX 	BITS {
		lowerCritical (0),
		lowerWarning (1),
		upperWarning (2),
		upperCritical (3),
		disableall(4)
	}
	MAX-ACCESS  	read-write
	STATUS 	current
	DESCRIPTION 
		"A bit string indicating which line voltage alarm thresholds are enabled. Supported only on PDU Phase in case of Y connection."
	::= { pduInputPhaseConfigEntry 24 }
	
pduInputPhasePropertiesTable  OBJECT-TYPE
	SYNTAX SEQUENCE OF PduInputPhasePropertiesEntry
	MAX-ACCESS  	not-accessible
	STATUS 	current
	DESCRIPTION 
		"A table of PDU Input Phase properties"
	::= { pduInputPhase 3 }
	
pduInputPhasePropertiesEntry  OBJECT-TYPE
	SYNTAX 	PduInputPhasePropertiesEntry
	MAX-ACCESS  	not-accessible
	STATUS 	current
	DESCRIPTION 
		"An input phase properties entry containing objects for a particular input phase."
	INDEX { pduUnitPropertiesIndex, pduInputPhasePropertiesIndex }
	::= { pduInputPhasePropertiesTable 1 }

PduInputPhasePropertiesEntry ::= SEQUENCE {
	pduInputPhasePropertiesIndex
		Integer32,
	pduInputPhasePropertiesCount
		Integer32
	}

pduInputPhasePropertiesIndex  OBJECT-TYPE
	SYNTAX 	Integer32 (1..256)
	MAX-ACCESS  	not-accessible
	STATUS 	current
	DESCRIPTION 
		"The index of the PDU Input Phase status entry"
	::= { pduInputPhasePropertiesEntry 1 }
	
pduInputPhasePropertiesCount  OBJECT-TYPE
	SYNTAX 	Integer32 (1..256)
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"The numeric Input Phase ID"
	::= { pduInputPhasePropertiesEntry 2 }
	
pduInputPhaseStatusTable  OBJECT-TYPE
	SYNTAX SEQUENCE OF PduInputPhaseStatusEntry
	MAX-ACCESS  	not-accessible
	STATUS 	current
	DESCRIPTION 
		"A table of PDU Input Phase status data"
	::= { pduInputPhase 4 }
	
pduInputPhaseStatusEntry  OBJECT-TYPE
	SYNTAX 	PduInputPhaseStatusEntry
	MAX-ACCESS  	not-accessible
	STATUS 	current
	DESCRIPTION 
		"An input phase status entry containing objects for a particular input phase."
	INDEX { pduUnitStatusIndex, pduInputPhaseStatusIndex }
	::= { pduInputPhaseStatusTable 1 }

PduInputPhaseStatusEntry ::= SEQUENCE {
	pduInputPhaseStatusIndex
		Integer32,
	pduInputPhaseStatusCount
		Integer32,
	pduInputPhaseStatusCurrentState
		INTEGER,
	pduInputPhaseStatusVoltageState
		INTEGER,
	pduInputPhaseStatusCurrent
		Integer32,
	pduInputPhaseStatusVoltage
		Integer32,
	pduInputPhaseStatusActivePower
		Integer32,
	pduInputPhaseStatusApparentPower
		Integer32,
	pduInputPhaseStatusPowerFactor
		Integer32,
	pduInputPhaseStatusLineVoltageState
		INTEGER,
	pduInputPhaseStatusLineVoltage
		Integer32
	}

pduInputPhaseStatusIndex  OBJECT-TYPE
	SYNTAX 	Integer32 (1..256)
	MAX-ACCESS  	not-accessible
	STATUS 	current
	DESCRIPTION 
		"The index of the PDU Input Phase status entry"
	::= { pduInputPhaseStatusEntry 1 }
	
pduInputPhaseStatusCount  OBJECT-TYPE
	SYNTAX 	Integer32 (1..256)
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"The numeric Input Phase ID"
	::= { pduInputPhaseStatusEntry 2 }
	
pduInputPhaseStatusCurrentState  OBJECT-TYPE
	SYNTAX 	INTEGER {
		upperCritical (1),
		upperWarning (2),
		lowerWarning (3),
		lowerCritical (4),
		normal (5)
	}
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"Indicates the present current status of the PDU Phase in case of Y connection or PDU Line in case of Delta conneciton."
	::= { pduInputPhaseStatusEntry 3 }
	
pduInputPhaseStatusVoltageState  OBJECT-TYPE
	SYNTAX 	INTEGER {
		upperCritical (1),
		upperWarning (2),
		lowerWarning (3),
		lowerCritical (4),
		normal (5)
	}
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"Indicates the present voltage status of the PDU Input Phase being queried"
	::= { pduInputPhaseStatusEntry 4 }
	
pduInputPhaseStatusCurrent  OBJECT-TYPE
	SYNTAX 	Integer32
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"Returns the current draw, in hundredths of Amps(A)"
	::= { pduInputPhaseStatusEntry 5 }
	
pduInputPhaseStatusVoltage  OBJECT-TYPE
	SYNTAX 	Integer32
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"Returns the voltage, in Volts(V)"
	::= { pduInputPhaseStatusEntry 6 }
	
pduInputPhaseStatusActivePower  OBJECT-TYPE
	SYNTAX 	Integer32
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"Returns power consumption, in Watts(W)"
	::= { pduInputPhaseStatusEntry 7 }
	
pduInputPhaseStatusApparentPower  OBJECT-TYPE
	SYNTAX 	Integer32
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"Returns power consumption, in Volt-Amps(VA)"
	::= { pduInputPhaseStatusEntry 8 }
	
pduInputPhaseStatusPowerFactor  OBJECT-TYPE
	SYNTAX 	Integer32
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"Returns the ratio of active to apparent power of the PDU, in the hundreths of PowerFactor."
	::= { pduInputPhaseStatusEntry 9 }
	
pduInputPhaseStatusLineVoltageState  OBJECT-TYPE
	SYNTAX 	INTEGER {
		upperCritical (1),
		upperWarning (2),
		lowerWarning (3),
		lowerCritical (4),
		normal (5)
	}
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"Indicates the present line voltage STATUS of the PDU Input Phase being queried. Supported only on PDU Phase in case of Y connection."
	::= { pduInputPhaseStatusEntry 10 }

pduInputPhaseStatusLineVoltage  OBJECT-TYPE
	SYNTAX 	Integer32
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"Returns the line voltage, in Volts(V). Supported only on PDU Phase in case of Y connection."
	::= { pduInputPhaseStatusEntry 11 }

-- Start pduCircuitBreaker
pduCircuitBreakerTableSize  OBJECT-TYPE
	SYNTAX 	Integer32 (1..256)
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"The number of PDU Circuit Breakers"
	::= { pduCircuitBreaker 1 }
	
pduCircuitBreakerConfigTable  OBJECT-TYPE
	SYNTAX SEQUENCE OF PduCircuitBreakerConfigEntry
	MAX-ACCESS  	not-accessible
	STATUS 	current
	DESCRIPTION 
		"A table of PDU Circuit Breaker configuration data"
	::= { pduCircuitBreaker 2 }
	
pduCircuitBreakerConfigEntry  OBJECT-TYPE
	SYNTAX 	PduCircuitBreakerConfigEntry
	MAX-ACCESS  	not-accessible
	STATUS 	current
	DESCRIPTION 
		"A circuit breaker configuration entry containing objects for a particular circuit breaker."
	INDEX { pduUnitConfigIndex, pduCircuitBreakerConfigIndex }
	::= { pduCircuitBreakerConfigTable 1 }

PduCircuitBreakerConfigEntry ::= SEQUENCE {
	pduCircuitBreakerConfigIndex
		Integer32,
	pduCircuitBreakerConfigCount
		Integer32,
	pduCircuitBreakerName
		DisplayString,
	pduCircuitBreakerConfigOverloadRestriction
		INTEGER,
	pduCircuitBreakerConfigLowerCriticalThreshold
		Unsigned32,
	pduCircuitBreakerConfigLowerWarningThreshold
		Unsigned32,
	pduCircuitBreakerConfigUpperCriticalThreshold
		Unsigned32,
	pduCircuitBreakerConfigUpperWarningThreshold
		Unsigned32,
	pduCircuitBreakerConfigAlarmResetThreshold
		Unsigned32,
	pduCircuitBreakerConfigAlarmStateChangeDelay
		Unsigned32,
	pduCircuitBreakerConfigEnabledThresholds
		BITS
	}

pduCircuitBreakerConfigIndex  OBJECT-TYPE
	SYNTAX 	Integer32 (1..256)
	MAX-ACCESS  	not-accessible
	STATUS 	current
	DESCRIPTION 
		"The index of the PDU Circuit Breaker configuration table entry"
	::= { pduCircuitBreakerConfigEntry 1 }
	
pduCircuitBreakerConfigCount  OBJECT-TYPE
	SYNTAX 	Integer32 (0..255)
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"The number of circuit breakers on the PDU"
	::= { pduCircuitBreakerConfigEntry 2 }
	
pduCircuitBreakerName  OBJECT-TYPE
	SYNTAX 	DisplayString
	MAX-ACCESS  	read-write
	STATUS 	current
	DESCRIPTION 
		"The label of the circuit breaker"
	::= { pduCircuitBreakerConfigEntry 3 }
	
pduCircuitBreakerConfigOverloadRestriction  OBJECT-TYPE
	SYNTAX 	INTEGER {
		alwaysAllowTurnOn (1),
		restrictOnUpperWarning (2),
		restrictOnUpperCritical (3),
		notSupported (4)
	}
	MAX-ACCESS  	read-write
	STATUS 	current
	DESCRIPTION 
		"This OID controls the behavior of a Switched PDU Circuit 
		Breaker when an overload condition is possible and additional 
		outlets are requested to be turned on. Setting this OID to 
		alwaysAllowTurnON (1) will always allow the outlets on the 
		corresponding Circuit Breaker to turn on. Setting this OID 
		to restrictOnUpperWarning (2) will not allow outlets on the 
		corresponding Circuit Breaker to turn on if the 
		pduCircuitBreakerConfigUpperWarningThreshold OID is exceeded. 
		Setting this OID to restrictOnUpperCritical (3) will not 
		allow outlets on the corresponding Circuit Breaker to turn 
		on if the pduCircuitBreakerConfigUpperCriticalThreshold OID 
		is exceeded. Models that do not support this feature will 
		respond to this OID with a value of notSupported (4). 
		Attempts to set this OID in these models will fail. "
	::= { pduCircuitBreakerConfigEntry 4 }

pduCircuitBreakerConfigLowerCriticalThreshold  OBJECT-TYPE
	SYNTAX 	Unsigned32
	MAX-ACCESS  	read-write
	STATUS 	current
	DESCRIPTION 
		"User-defined lower critical circuit breaker current alarm threshold in hundredths of Amps(A)."
	::= { pduCircuitBreakerConfigEntry 5 }
	
pduCircuitBreakerConfigLowerWarningThreshold  OBJECT-TYPE
	SYNTAX 	Unsigned32
	MAX-ACCESS  	read-write
	STATUS 	current
	DESCRIPTION 
		"User-defined lower non-critical (warning) circuit breaker current alarm threshold in hundredths of Amps(A)."
	::= { pduCircuitBreakerConfigEntry 6 }
	
pduCircuitBreakerConfigUpperCriticalThreshold  OBJECT-TYPE
	SYNTAX 	Unsigned32
	MAX-ACCESS  	read-write
	STATUS 	current
	DESCRIPTION 
		"User-defined upper critical circuit breaker current alarm threshold in hundredths of Amps(A)."
	::= { pduCircuitBreakerConfigEntry 7 }
	
pduCircuitBreakerConfigUpperWarningThreshold  OBJECT-TYPE
	SYNTAX 	Unsigned32
	MAX-ACCESS  	read-write
	STATUS 	current
	DESCRIPTION 
		"User-defined upper non-critical (warning) circuit breaker current alarm threshold in hundredths of Amps(A)."
	::= { pduCircuitBreakerConfigEntry 8 }
	
pduCircuitBreakerConfigAlarmResetThreshold  OBJECT-TYPE
	SYNTAX 	Unsigned32
	MAX-ACCESS  	read-write
	STATUS 	current
	DESCRIPTION 
		"The hysteresis used for deassertions in hundredths of Amps(A)."
	::= { pduCircuitBreakerConfigEntry 9 }
	
pduCircuitBreakerConfigAlarmStateChangeDelay  OBJECT-TYPE
	SYNTAX 	Unsigned32
	MAX-ACCESS  	read-write
	STATUS 	current
	DESCRIPTION 
		"The delay measured in samples before a state is asserted. 
		If the value is zero, then the state is asserted as soon 
		as it is detected; if it is non-zero, say n, then the 
		assertion condition must exist for n+1 consecutive samples 
		before the corresponding assertion event is reported."
	::= { pduCircuitBreakerConfigEntry 10 }
	
pduCircuitBreakerConfigEnabledThresholds  OBJECT-TYPE
	SYNTAX 	BITS {
		lowerCritical (0),
		lowerWarning (1),
		upperWarning (2),
		upperCritical (3)
	}
	MAX-ACCESS  	read-write
	STATUS 	current
	DESCRIPTION 
		"A bit string indicating which alarm thresholds are enabled."
	::= { pduCircuitBreakerConfigEntry 11 }

pduCircuitBreakerPropertiesTable  OBJECT-TYPE
	SYNTAX SEQUENCE OF PduCircuitBreakerPropertiesEntry
	MAX-ACCESS  	not-accessible
	STATUS 	current
	DESCRIPTION 
		"A table of PDU circuit breaker properties"
	::= { pduCircuitBreaker 3 }

pduCircuitBreakerPropertiesEntry  OBJECT-TYPE
	SYNTAX 	PduCircuitBreakerPropertiesEntry
	MAX-ACCESS  	not-accessible
	STATUS 	current
	DESCRIPTION 
		"A circuit breaker properties entry containing objects for a particular circuit breaker."
	INDEX { pduUnitPropertiesIndex, pduCircuitBreakerPropertiesIndex }
	::= { pduCircuitBreakerPropertiesTable 1 }

PduCircuitBreakerPropertiesEntry ::= SEQUENCE {
	pduCircuitBreakerPropertiesIndex
		Integer32,
	pduCircuitBreakerPropertiesCount
		Integer32,
	pduCircuitBreakerPropertiesInputLayout
		INTEGER,
	pduCircuitBreakerPropertiesCurrentRating
		Integer32
	}

pduCircuitBreakerPropertiesIndex  OBJECT-TYPE
	SYNTAX 	Integer32 (1..256)
	MAX-ACCESS  	not-accessible
	STATUS 	current
	DESCRIPTION 
		"The index of the PDU Circuit Breaker properties table entry"
	::= { pduCircuitBreakerPropertiesEntry 1 }
	
pduCircuitBreakerPropertiesCount  OBJECT-TYPE
	SYNTAX 	Integer32 (0..255)
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"The number of Circuit Breakers"
	::= { pduCircuitBreakerPropertiesEntry 2 }
	
pduCircuitBreakerPropertiesInputLayout  OBJECT-TYPE
	SYNTAX 	INTEGER {
		seqPhase1ToNeutral (1),
		seqPhase2ToNeutral (2),
		seqPhase3ToNeutral (3),
		seqPhase1ToPhase2 (4),
		seqPhase2ToPhase3 (5),
		seqPhase3ToPhase1 (6)
	}
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"This OID describes the outlet phase connections on 
		the referenced bank as follows: 
		seqPhase1ToNeutral(1) indicates that outlets attached 
		to circuit breaker are connected from Phase 1 to Neutral. 
		seqPhase2ToNeutral(2) indicates that outlets attached 
		to circuit breaker are connected from Phase 2 to Neutral. 
		seqPhase3ToNeutral(3) indicates that outlets attached 
		to circuit breaker are connected from Phase 3 to Neutral. 
		seqPhase1ToPhase2(4) indicates that outlets attached 
		to circuit breaker are connected from Phase 1 to Phase2. 
		seqPhase2ToPhase3(5) indicates that outlets attached 
		to circuit breaker are connected from Phase 2 to Phase3.  
		seqPhase3ToPhase1(6) indicates that outlets attached 
		to circuit breaker are connected from Phase 3 to Phase1. "
	::= { pduCircuitBreakerPropertiesEntry 3 }

pduCircuitBreakerPropertiesCurrentRating  OBJECT-TYPE
	SYNTAX 	Integer32 (0..255)
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"The number of Circuit Breakers"
	::= { pduCircuitBreakerPropertiesEntry 4 }

pduCircuitBreakerStatusTable  OBJECT-TYPE
	SYNTAX SEQUENCE OF PduCircuitBreakerStatusEntry
	MAX-ACCESS  	not-accessible
	STATUS 	current
	DESCRIPTION 
		"A table of PDU circuit breaker status data"
	::= { pduCircuitBreaker 4 }
	
pduCircuitBreakerStatusEntry  OBJECT-TYPE
	SYNTAX 	PduCircuitBreakerStatusEntry
	MAX-ACCESS  	not-accessible
	STATUS 	current
	DESCRIPTION 
		"A circuit breaker status entry containing objects for a particular circuit breaker."
	INDEX { pduUnitStatusIndex, pduCircuitBreakerStatusIndex }
	::= { pduCircuitBreakerStatusTable 1 }

PduCircuitBreakerStatusEntry ::= SEQUENCE {
	pduCircuitBreakerStatusIndex
		Integer32,
	pduCircuitBreakerStatusCount
		Integer32,
	pduCircuitBreakerLabel
		DisplayString,
	pduCircuitBreakerStatusLoadState
		INTEGER,
	pduCircuitBreakerStatusCurrent
		Integer32,
	pduCircuitBreakerStatusPowerFactor
		Integer32
	}

pduCircuitBreakerStatusIndex  OBJECT-TYPE
	SYNTAX 	Integer32 (1..256)
	MAX-ACCESS  	not-accessible
	STATUS 	current
	DESCRIPTION 
		"The index of the PDU Circuit Breaker status table entry"
	::= { pduCircuitBreakerStatusEntry 1 }
	
pduCircuitBreakerStatusCount  OBJECT-TYPE
	SYNTAX 	Integer32 (0..255)
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"The number of Circuit Breakers"
	::= { pduCircuitBreakerStatusEntry 2 }
	
pduCircuitBreakerLabel  OBJECT-TYPE
	SYNTAX 	DisplayString
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"The label on the PDU identifying the circuit breaker"
	::= { pduCircuitBreakerStatusEntry 3 }
	
pduCircuitBreakerStatusLoadState  OBJECT-TYPE
	SYNTAX 	INTEGER {
		upperCritical (1),
		upperWarning (2),
		lowerWarning (3),
		lowerCritical (4),
		normal (5),
		off (6)
	}
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"Indicates the present load status of the PDU Circuit 
		Breaker being queried"
	::= { pduCircuitBreakerStatusEntry 4 }
	
pduCircuitBreakerStatusCurrent  OBJECT-TYPE
	SYNTAX 	Integer32
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"Returns the current draw, in hundredths of Amps(A), of the load on 
		the PDU Circuit Breaker being queried."
	::= { pduCircuitBreakerStatusEntry 5 }
	
pduCircuitBreakerStatusPowerFactor  OBJECT-TYPE
	SYNTAX 	Integer32
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"Returns the ratio of active to apparent power of the Circuit Breaker, in the hundreths of PowerFactor."
	::= { pduCircuitBreakerStatusEntry 6 }

-- Start pduOutlet
pduOutletSwitchedTableSize  OBJECT-TYPE
	SYNTAX 	Integer32 (1..256)
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"The number of PDU Outlets"
	::= { pduOutlet 1 }

pduOutletSwitchedConfigTable  OBJECT-TYPE
	SYNTAX SEQUENCE OF PduOutletSwitchedConfigEntry
	MAX-ACCESS  	not-accessible
	STATUS 	current
	DESCRIPTION 
		"A table of PDU Switched Outlet configuration data"
	::= { pduOutlet 2 }
	
pduOutletSwitchedConfigEntry  OBJECT-TYPE
	SYNTAX 	PduOutletSwitchedConfigEntry
	MAX-ACCESS  	not-accessible
	STATUS 	current
	DESCRIPTION 
		"An outlet configuration entry containing objects for a particular outlet."
	INDEX { pduUnitConfigIndex, pduOutletSwitchedConfigIndex }
	::= { pduOutletSwitchedConfigTable 1 }

PduOutletSwitchedConfigEntry ::= SEQUENCE {
	pduOutletSwitchedConfigIndex
		Integer32,
	pduOutletSwitchedName
		DisplayString,
	pduOutletSwitchedStateOnStartup
		INTEGER,
	pduOutletSwitchedConfigPowerOnTime
		Integer32,
	pduOutletSwitchedConfigPowerOffTime
		Integer32,
	pduOutletSwitchedConfigRebootDuration
		Integer32
	}

pduOutletSwitchedConfigIndex  OBJECT-TYPE
	SYNTAX 	Integer32 (1..256)
	MAX-ACCESS  	not-accessible
	STATUS 	current
	DESCRIPTION 
		"The index of the PDU Switched Outlet configuration table entry"
	::= { pduOutletSwitchedConfigEntry 1 }

pduOutletSwitchedName  OBJECT-TYPE
	SYNTAX 	DisplayString
	MAX-ACCESS  	read-write
	STATUS 	current
	DESCRIPTION 
		"The user-defined name for the Switched Outlet"
	::= { pduOutletSwitchedConfigEntry 2 }

pduOutletSwitchedStateOnStartup  OBJECT-TYPE
	SYNTAX 	INTEGER {
		off (0),
		on (1),
		lastKnownState (2)
		}
	MAX-ACCESS  	read-write
	STATUS 	current
	DESCRIPTION 
		"The outlet state on device startup; overrides 
		the global value pduUnitConfigGlobalOutletStateOnStartup."
	::= { pduOutletSwitchedConfigEntry 3 }

pduOutletSwitchedConfigPowerOnTime  OBJECT-TYPE
	SYNTAX 	Integer32
	MAX-ACCESS  	read-write
	STATUS 	current
	DESCRIPTION 
		"The amount of delay, in seconds, between when power is 
		provided to outlets the outlet and when this outlet 
		starts providing power"
	::= { pduOutletSwitchedConfigEntry 4 }

pduOutletSwitchedConfigPowerOffTime  OBJECT-TYPE
	SYNTAX 	Integer32
	MAX-ACCESS  	read-write
	STATUS 	current
	DESCRIPTION 
		"The amount of time, in seconds, this outlet will delay 
		powering off"
	::= { pduOutletSwitchedConfigEntry 5 }

pduOutletSwitchedConfigRebootDuration  OBJECT-TYPE
	SYNTAX 	Integer32
	MAX-ACCESS  	read-write
	STATUS 	current
	DESCRIPTION 
		"The amount of time, in seconds, this outlet will remain 
		in powered off state before returning to power on state 
		during a reboot action."
	::= { pduOutletSwitchedConfigEntry 6 }
	
pduOutletSwitchedPropertiesTable  OBJECT-TYPE
	SYNTAX SEQUENCE OF PduOutletSwitchedPropertiesEntry
	MAX-ACCESS  	not-accessible
	STATUS 	current
	DESCRIPTION 
		"A table of PDU Switched Outlet properties"
	::= { pduOutlet 3 }
	
pduOutletSwitchedPropertiesEntry  OBJECT-TYPE
	SYNTAX 	PduOutletSwitchedPropertiesEntry
	MAX-ACCESS  	not-accessible
	STATUS 	current
	DESCRIPTION 
		"An outlet properties entry containing objects for a particular outlet."
	INDEX { pduUnitPropertiesIndex, pduOutletSwitchedPropertiesIndex }
	::= { pduOutletSwitchedPropertiesTable 1 }

PduOutletSwitchedPropertiesEntry ::= SEQUENCE {
	pduOutletSwitchedPropertiesIndex
		Integer32,
	pduOutletSwitchedPropertiesNumber
		Integer32,
	pduOutletSwitchedPropertiesName
		DisplayString,
	pduOutletSwitchedPropertiesInputPhaseLayout
		INTEGER,
	pduOutletSwitchedPropertiesCircuitBreaker
		Integer32,
	pduOutletSwitchedPropertiesCurrentRating
		Integer32
	}

pduOutletSwitchedPropertiesIndex  OBJECT-TYPE
	SYNTAX 	Integer32 (1..256)
	MAX-ACCESS  	not-accessible
	STATUS 	current
	DESCRIPTION 
		"The index of the PDU Switched Outlet properties table entry"
	::= { pduOutletSwitchedPropertiesEntry 1 }

pduOutletSwitchedPropertiesNumber  OBJECT-TYPE
	SYNTAX 	Integer32 (1..256)
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"The numeric Switched Outlet ID"
	::= { pduOutletSwitchedPropertiesEntry 2 }

pduOutletSwitchedPropertiesName  OBJECT-TYPE
	SYNTAX 	DisplayString
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"The user-defined switched outlet ID string"
	::= { pduOutletSwitchedPropertiesEntry 3 }
	
pduOutletSwitchedPropertiesInputPhaseLayout  OBJECT-TYPE
	SYNTAX 	INTEGER {
		seqPhase1ToNeutral (1),
		seqPhase2ToNeutral (2),
		seqPhase3ToNeutral (3),
		seqPhase1ToPhase2 (4),
		seqPhase2ToPhase3 (5),
		seqPhase3ToPhase1 (6)
	}
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"This OID describes the outlet phase connections 
		on the referenced bank as follows: 
		seqPhase1ToNeutral(1) indicates that outlets 
		attached to Switched Outlet are connected from Phase 1 to Neutral. 
		seqPhase2ToNeutral(2) indicates that outlets 
		attached to Switched Outlet are connected from Phase 2 to Neutral. 
		seqPhase3ToNeutral(3) indicates that outlets 
		attached to Switched Outlet are connected from Phase 3 to Neutral. 
		seqPhase1ToPhase2(4) indicates that outlets 
		attached to Switched Outlet are connected from Phase 1 to Phase2. 
		seqPhase2ToPhase3(5) indicates that outlets 
		attached to Switched Outlet are connected from Phase 2 to Phase3.  
		seqPhase3ToPhase1(6) indicates that outlets 
		attached to Switched Outlet are connected from Phase 3 to Phase1. "
	::= { pduOutletSwitchedPropertiesEntry 4 }

pduOutletSwitchedPropertiesCircuitBreaker  OBJECT-TYPE
	SYNTAX 	Integer32 (1..256)
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"The numeric Circuit Breaker ID"
	::= { pduOutletSwitchedPropertiesEntry 5 }
	
pduOutletSwitchedPropertiesCurrentRating  OBJECT-TYPE
	SYNTAX 	Integer32 (1..256)
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"The current rating of outlet in hundreths of ampere"
	::= { pduOutletSwitchedPropertiesEntry 6 }

pduOutletSwitchedStatusTable  OBJECT-TYPE
	SYNTAX SEQUENCE OF PduOutletSwitchedStatusEntry
	MAX-ACCESS  	not-accessible
	STATUS 	current
	DESCRIPTION 
		"A table of PDU Switched Outlet status data"
	::= { pduOutlet 4 }

pduOutletSwitchedStatusEntry  OBJECT-TYPE
	SYNTAX 	PduOutletSwitchedStatusEntry
	MAX-ACCESS  	not-accessible
	STATUS 	current
	DESCRIPTION 
		"Status data from the PDU Switched Outlet being queried"
	INDEX { pduUnitStatusIndex, pduOutletSwitchedStatusIndex }
	::= { pduOutletSwitchedStatusTable 1 }

PduOutletSwitchedStatusEntry ::= SEQUENCE {
	pduOutletSwitchedStatusIndex
		Integer32,
	pduOutletSwitchedStatusNumber
		Integer32,
	pduOutletSwitchedStatusName
		DisplayString,
	pduOutletSwitchedStatusState
		INTEGER
	}

pduOutletSwitchedStatusIndex  OBJECT-TYPE
	SYNTAX 	Integer32 (1..256)
	MAX-ACCESS  	not-accessible
	STATUS 	current
	DESCRIPTION 
		"The index of the PDU Switched Outlet status table entry"
	::= { pduOutletSwitchedStatusEntry 1 }

pduOutletSwitchedStatusNumber  OBJECT-TYPE
	SYNTAX 	Integer32 (1..256)
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"The numeric Switched Outlet ID"
	::= { pduOutletSwitchedStatusEntry 2 }

pduOutletSwitchedStatusName  OBJECT-TYPE
	SYNTAX 	DisplayString
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"The user-defined switched outlet ID string"
	::= { pduOutletSwitchedStatusEntry 3 }

pduOutletSwitchedStatusState  OBJECT-TYPE
	SYNTAX 	INTEGER {
		off (0),
		on (1)
	}
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"Indicates the present switch state of the 
		PDU switched outlet being queried"
	::= { pduOutletSwitchedStatusEntry 4 }
	
pduOutletSwitchedControlTable  OBJECT-TYPE
	SYNTAX SEQUENCE OF PduOutletSwitchedControlEntry
	MAX-ACCESS  	not-accessible
	STATUS 	current
	DESCRIPTION 
		"A table of PDU Switched Outlet status data"
	::= { pduOutlet 5 }
	
pduOutletSwitchedControlEntry  OBJECT-TYPE
	SYNTAX 	PduOutletSwitchedControlEntry
	MAX-ACCESS  	not-accessible
	STATUS 	current
	DESCRIPTION 
		"Status data from the PDU Switched Outlet 
		being queried"
	INDEX { pduUnitConfigIndex, pduOutletSwitchedControlIndex }
	::= { pduOutletSwitchedControlTable 1 }

PduOutletSwitchedControlEntry ::= SEQUENCE {
	pduOutletSwitchedControlIndex
		Integer32,
	pduOutletSwitchedControlNumber
		Integer32,
	pduOutletSwitchedControlName
		DisplayString,
	pduOutletSwitchedControlCommand
		INTEGER
	}

pduOutletSwitchedControlIndex  OBJECT-TYPE
	SYNTAX 	Integer32 (1..256)
	MAX-ACCESS  	not-accessible
	STATUS 	current
	DESCRIPTION 
		"The index to the PDU switched outlet 
		control data table entry"
	::= { pduOutletSwitchedControlEntry 1 }
	
pduOutletSwitchedControlNumber  OBJECT-TYPE
	SYNTAX 	Integer32 (1..256)
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"The numeric Switched Outlet ID"
	::= { pduOutletSwitchedControlEntry 2 }
	
pduOutletSwitchedControlName  OBJECT-TYPE
	SYNTAX 	DisplayString
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"The user-defined switched outlet ID string"
	::= { pduOutletSwitchedControlEntry 3 }

pduOutletSwitchedControlCommand  OBJECT-TYPE
	SYNTAX 	INTEGER {
		immediateOff (1),
		immediateOn (2),
		delayedOff (3),
		delayedOn (4),
		immediateReboot (5),
		delayedReboot (6),
		outletUnknown (7)
		}
	MAX-ACCESS  	read-write
	STATUS 	current
	DESCRIPTION 
		"Getting this variable will return the outlet state.
		If the outlet is on, the immediateOn (2) 
		value will be returned. If the outlet is off, 
		the immediateOff (1) value will be returned. 
		If the state of the outlet cannot be determined, the 
		outletUnknown (7) value will be returned. If the 
		outletUnknown condition should occur, all devices 
		powered by the PDU should be shut down. The PDU's 
		power should then be cycled to clear this condition. 
		Setting this variable to immediateOn (2) will immediately 
		turn the outlet on. Setting this variable to 
		immediateOff (1) will immediately turn the outlet off. 
		Setting this variable to immediateReboot (5) 
		will cause the Switched PDU to perform an immediateOff 
		command, wait the pduOutletSwitchedConfigRebootDuration 
		OID time, and then perform an immediateOn command.
		Setting this variable to delayedOn (4) will turn the 
		outlet on after the pduOutletSwitchedConfigPowerOnTime 
		OID time has elapsed. Setting this variable to 
		delayedOff (3) will turn the outlet off after the 
		pduOutletSwitchedConfigPowerOffTime OID time has elapsed. 
		Setting this variable to delayedReboot  (6) will cause 
		the Switched PDU to perform a delayedOff command, wait 
		the pduOutletSwitchedConfigRebootDuration OID time, and 
		then perform a delayedOn command."
	::= { pduOutletSwitchedControlEntry 4 }

pduOutletMeteredTableSize  OBJECT-TYPE
	SYNTAX 	Integer32 (1..256)
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"The number of PDU Outlets"
	::= { pduOutlet 6 }

pduOutletMeteredConfigTable  OBJECT-TYPE
	SYNTAX SEQUENCE OF PduOutletMeteredConfigEntry
	MAX-ACCESS  	not-accessible
	STATUS 	current
	DESCRIPTION 
		"A table of PDU Metered Outlet configuration data"
	::= { pduOutlet 7 }

pduOutletMeteredConfigEntry  OBJECT-TYPE
	SYNTAX 	PduOutletMeteredConfigEntry
	MAX-ACCESS  	not-accessible
	STATUS 	current
	DESCRIPTION 
		"An outlet configuration entry containing objects for a particular outlet."
	INDEX { pduUnitConfigIndex, pduOutletMeteredConfigIndex }
	::= { pduOutletMeteredConfigTable 1 }

PduOutletMeteredConfigEntry ::= SEQUENCE {
	pduOutletMeteredConfigIndex
		Integer32,
	pduOutletMeteredName
		DisplayString,
	pduOutletMeteredConfigLowerCriticalThreshold
		Unsigned32,
	pduOutletMeteredConfigLowerWarningThreshold
		Unsigned32,
	pduOutletMeteredConfigUpperCriticalThreshold
		Unsigned32,
	pduOutletMeteredConfigUpperWarningThreshold
		Unsigned32,
	pduOutletMeteredConfigAlarmResetThreshold
		Unsigned32,
	pduOutletMeteredConfigAlarmStateChangeDelay
		Unsigned32,
	pduOutletMeteredConfigEnabledThresholds
		BITS
	}

pduOutletMeteredConfigIndex  OBJECT-TYPE
	SYNTAX 	Integer32 (1..256)
	MAX-ACCESS  	not-accessible
	STATUS 	current
	DESCRIPTION 
		"The index of the PDU Metered Outlet 
		configuration table entry"
	::= { pduOutletMeteredConfigEntry 1 }

pduOutletMeteredName  OBJECT-TYPE
	SYNTAX 	DisplayString
	MAX-ACCESS  	read-write
	STATUS 	current
	DESCRIPTION 
		"The user-defined name for the Metered Outlet"
	::= { pduOutletMeteredConfigEntry 2 }

pduOutletMeteredConfigLowerCriticalThreshold  OBJECT-TYPE
	SYNTAX 	Unsigned32
	MAX-ACCESS  	read-write
	STATUS 	current
	DESCRIPTION 
		"User-defined lower critical outlet active power alarm threshold in Watts(W)."
	::= { pduOutletMeteredConfigEntry 3 }

pduOutletMeteredConfigLowerWarningThreshold  OBJECT-TYPE
	SYNTAX 	Unsigned32
	MAX-ACCESS  	read-write
	STATUS 	current
	DESCRIPTION 
		"User-defined lower non-critical (warning) outlet active power alarm threshold in Watts(W)."
	::= { pduOutletMeteredConfigEntry 4 }

pduOutletMeteredConfigUpperCriticalThreshold  OBJECT-TYPE
	SYNTAX 	Unsigned32
	MAX-ACCESS  	read-write
	STATUS 	current
	DESCRIPTION 
		"User-defined upper critical outlet active power alarm threshold in Watts(W)."
	::= { pduOutletMeteredConfigEntry 5 }

pduOutletMeteredConfigUpperWarningThreshold  OBJECT-TYPE
	SYNTAX 	Unsigned32
	MAX-ACCESS  	read-write
	STATUS 	current
	DESCRIPTION 
		"User-defined upper non-critical (warning) outlet active power alarm threshold in Watts(W)."
	::= { pduOutletMeteredConfigEntry 6 }

pduOutletMeteredConfigAlarmResetThreshold  OBJECT-TYPE
	SYNTAX 	Unsigned32
	MAX-ACCESS  	read-write
	STATUS 	current
	DESCRIPTION 
		"The hysteresis used for deassertions in Watts(W)."
	::= { pduOutletMeteredConfigEntry 7 }

pduOutletMeteredConfigAlarmStateChangeDelay  OBJECT-TYPE
	SYNTAX 	Unsigned32
	MAX-ACCESS  	read-write
	STATUS 	current
	DESCRIPTION 
		"The delay measured in samples before a state 
		is asserted. If the value is zero, then the state 
		is asserted as soon as it is detected; if it is 
		non-zero, say n, then the assertion condition must 
		exist for n+1 consecutive samples before the 
		corresponding assertion event is reported."
	::= { pduOutletMeteredConfigEntry 8 }

pduOutletMeteredConfigEnabledThresholds  OBJECT-TYPE
	SYNTAX 	BITS {
		lowerCritical (0),
		lowerWarning (1),
		upperWarning (2),
		upperCritical (3)
	}
	MAX-ACCESS  	read-write
	STATUS 	current
	DESCRIPTION 
		"A bit string indicating which alarm 
		thresholds are enabled."
	::= { pduOutletMeteredConfigEntry 9 }

pduOutletMeteredPropertiesTable  OBJECT-TYPE
	SYNTAX SEQUENCE OF PduOutletMeteredPropertiesEntry
	MAX-ACCESS  	not-accessible
	STATUS 	current
	DESCRIPTION 
		"A table of PDU Metered Outlet properties"
	::= { pduOutlet 8 }

pduOutletMeteredPropertiesEntry  OBJECT-TYPE
	SYNTAX 	PduOutletMeteredPropertiesEntry
	MAX-ACCESS  	not-accessible
	STATUS 	current
	DESCRIPTION 
		"Configuration data from the PDU Metered 
		Outlet being queried"
	INDEX { pduUnitPropertiesIndex, pduOutletMeteredPropertiesIndex }
	::= { pduOutletMeteredPropertiesTable 1 }

PduOutletMeteredPropertiesEntry ::= SEQUENCE {
	pduOutletMeteredPropertiesIndex
		Integer32,
	pduOutletMeteredPropertiesNumber
		Integer32,
	pduOutletMeteredPropertiesName
		DisplayString,
	pduOutletMeteredPropertiesInputPhaseLayout
		INTEGER,
	pduOutletMeteredPropertiesCircuitBreaker
		Integer32,
	pduOutletMeteredPropertiesPowerRating
		Integer32,
	pduOutletMeteredPropertiesCurrentRating
		Integer32
	}

pduOutletMeteredPropertiesIndex  OBJECT-TYPE
	SYNTAX 	Integer32 (1..256)
	MAX-ACCESS  	not-accessible
	STATUS 	current
	DESCRIPTION 
		"The index of the PDU Metered Outlet 
		properties table entry"
	::= { pduOutletMeteredPropertiesEntry 1 }

pduOutletMeteredPropertiesNumber  OBJECT-TYPE
	SYNTAX 	Integer32 (1..256)
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"The numeric Metered Outlet ID"
	::= { pduOutletMeteredPropertiesEntry 2 }

pduOutletMeteredPropertiesName  OBJECT-TYPE
	SYNTAX 	DisplayString
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"The user-defined Metered outlet ID string"
	::= { pduOutletMeteredPropertiesEntry 3 }

pduOutletMeteredPropertiesInputPhaseLayout  OBJECT-TYPE
	SYNTAX 	INTEGER {
		seqPhase1ToNeutral (1),
		seqPhase2ToNeutral (2),
		seqPhase3ToNeutral (3),
		seqPhase1ToPhase2 (4),
		seqPhase2ToPhase3 (5),
		seqPhase3ToPhase1 (6)
	}
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"This OID describes the outlet phase connections 
		on the referenced bank as follows: 
		seqPhase1ToNeutral(1) indicates that outlets attached 
		to Metered Outlet are connected from Phase 1 to Neutral. 
		seqPhase2ToNeutral(2) indicates that outlets attached 
		to Metered Outlet are connected from Phase 2 to Neutral. 
		seqPhase3ToNeutral(3) indicates that outlets attached 
		to Metered Outlet are connected from Phase 3 to Neutral. 
		seqPhase1ToPhase2(4) indicates that outlets attached 
		to Metered Outlet are connected from Phase 1 to Phase2. 
		seqPhase2ToPhase3(5) indicates that outlets attached 
		to Metered Outlet are connected from Phase 2 to Phase3.  
		seqPhase3ToPhase1(6) indicates that outlets attached 
		to Metered Outlet are connected from Phase 3 to Phase1. "
	::= { pduOutletMeteredPropertiesEntry 4 }

pduOutletMeteredPropertiesCircuitBreaker  OBJECT-TYPE
	SYNTAX 	Integer32 (1..256)
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"The numeric Circuit Breaker ID"
	::= { pduOutletMeteredPropertiesEntry 5 }

pduOutletMeteredPropertiesPowerRating  OBJECT-TYPE
	SYNTAX 	Integer32
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"Maximum power rating of the PDU metered outlet"
	::= { pduOutletMeteredPropertiesEntry 6 }

pduOutletMeteredPropertiesCurrentRating  OBJECT-TYPE
	SYNTAX 	Integer32
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"Metered outlet current rating in hundreths of ampere"
	::= { pduOutletMeteredPropertiesEntry 7 }
	
pduOutletMeteredStatusTable  OBJECT-TYPE
	SYNTAX SEQUENCE OF PduOutletMeteredStatusEntry
	MAX-ACCESS  	not-accessible
	STATUS 	current
	DESCRIPTION 
		"A table of PDU Metered Outlet status data"
	::= { pduOutlet 9 }
	
pduOutletMeteredStatusEntry  OBJECT-TYPE
	SYNTAX 	PduOutletMeteredStatusEntry
	MAX-ACCESS  	not-accessible
	STATUS 	current
	DESCRIPTION 
		"Status data from the PDU Metered Outlet being queried"
	INDEX { pduUnitStatusIndex, pduOutletMeteredStatusIndex }
	::= { pduOutletMeteredStatusTable 1 }

PduOutletMeteredStatusEntry ::= SEQUENCE {
	pduOutletMeteredStatusIndex
		Integer32,
	pduOutletMeteredStatusNumber
		Integer32,
	pduOutletMeteredStatusName
		DisplayString,
	pduOutletMeteredStatusLoadState
		INTEGER,
	pduOutletMeteredStatusCurrent
		Integer32,
	pduOutletMeteredStatusActivePower
		Integer32,
	pduOutletMeteredStatusPowerFactor
		Integer32,
	pduOutletMeteredStatusPeakPower
		Integer32,
	pduOutletMeteredStatusPeakPowerTimeStamp
		DisplayString,
	pduOutletMeteredStatusPeakPowerStartTime
		DisplayString,
	pduOutletMeteredStatusResettableEnergy
		Integer32
	}

pduOutletMeteredStatusIndex  OBJECT-TYPE
	SYNTAX 	Integer32 (1..256)
	MAX-ACCESS  	not-accessible
	STATUS 	current
	DESCRIPTION 
		"The index of the PDU Metered Outlet status table entry"
	::= { pduOutletMeteredStatusEntry 1 }

pduOutletMeteredStatusNumber  OBJECT-TYPE
	SYNTAX 	Integer32 (1..256)
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"The numeric Metered Outlet ID"
	::= { pduOutletMeteredStatusEntry 2 }

pduOutletMeteredStatusName  OBJECT-TYPE
	SYNTAX 	DisplayString
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"The user-defined Metered outlet ID string"
	::= { pduOutletMeteredStatusEntry 3 }
	
pduOutletMeteredStatusLoadState  OBJECT-TYPE
	SYNTAX 	INTEGER {
		upperCritical (1),
		upperWarning (2),
		lowerWarning (3),
		lowerCritical (4),
		normal (5)
	}
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"Returns the present load status of the PDU metered outlet being queried."
	::= { pduOutletMeteredStatusEntry 4 }

pduOutletMeteredStatusCurrent  OBJECT-TYPE
	SYNTAX 	Integer32
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"Returns the current draw, in hundredths of Amps(A), of the load on the PDU 
		outlet being queried."
	::= { pduOutletMeteredStatusEntry 5 }

pduOutletMeteredStatusActivePower  OBJECT-TYPE
	SYNTAX 	Integer32
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"Returns the power draw, in Watts(W), of the load 
		on the PDU outlet being queried."
	::= { pduOutletMeteredStatusEntry 6 }
	
pduOutletMeteredStatusPowerFactor  OBJECT-TYPE
	SYNTAX 	Integer32
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"Returns the ratio of active to apparent power 
		of the PDU Outlet being queried, in the hundreths of PowerFactor."
	::= { pduOutletMeteredStatusEntry 7 }

pduOutletMeteredStatusPeakPower  OBJECT-TYPE
	SYNTAX 	Integer32
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"Returns peak power consumption, in Watts(W), 
		of the Rack PDU outlet being queried."
	::= { pduOutletMeteredStatusEntry 8 }

pduOutletMeteredStatusPeakPowerTimeStamp  OBJECT-TYPE
	SYNTAX 	DisplayString
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"Indicates the date and time that this metered 
		outlet's peak power consumption occurred"
	::= { pduOutletMeteredStatusEntry 9 }

pduOutletMeteredStatusPeakPowerStartTime  OBJECT-TYPE
	SYNTAX 	DisplayString
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"Indicates the start date and time that this metered 
		outlet began recording peak power observations"
	::= { pduOutletMeteredStatusEntry 10 }

pduOutletMeteredStatusResettableEnergy  OBJECT-TYPE
	SYNTAX 	Integer32
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"A user resettable energy meter measuring outlet load energy 
		consumption in tenths of Kilowatt-Hours(kWh)."
	::= { pduOutletMeteredStatusEntry 11 }

-- Start pduExternalSensor
pduExternalSensorTableSize  OBJECT-TYPE
	SYNTAX 	Integer32 (1..256)
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"The total number of External Sensors"
	::= { pduExternalSensor 1 }

pduExternalSensorNamePlateTable  OBJECT-TYPE
	SYNTAX SEQUENCE OF PduExternalSensorNamePlateEntry
	MAX-ACCESS  	not-accessible
	STATUS 	current
	DESCRIPTION 
		"A table of PDU ExternalSensorNamePlate data"
	::= { pduExternalSensor 2 }

pduExternalSensorNamePlateEntry  OBJECT-TYPE
	SYNTAX 	PduExternalSensorNamePlateEntry
	MAX-ACCESS  	not-accessible
	STATUS 	current
	DESCRIPTION 
		"External Sensor Name Plate data from the external 
		sensor being queried. The number of entries equals 
		the value of pduExternalSensorNamePlateTableSize."
	INDEX { pduNamePlateIndex, pduExternalSensorNamePlateIndex }
	::= { pduExternalSensorNamePlateTable 1 }

PduExternalSensorNamePlateEntry ::= SEQUENCE {
	pduExternalSensorNamePlateIndex
		Integer32,
	pduExternalSensorNamePlateName
		DisplayString,
	pduExternalSensorNamePlateDescription
		DisplayString,
	pduExternalSensorNamePlateLocation
		DisplayString,
	pduExternalSensorNamePlateSerialNumber
		DisplayString,
	pduExternalSensorNamePlateType
		INTEGER,
	pduExternalSensorNamePlateUnits
		INTEGER,
	pduExternalSensorNamePlateIdentifier
		Integer32,
	pduExternalSensorNamePlateProductCode
		DisplayString
	}

pduExternalSensorNamePlateIndex  OBJECT-TYPE
	SYNTAX 	Integer32 (0..255)
	MAX-ACCESS  	not-accessible
	STATUS 	current
	DESCRIPTION 
		"The index of the PDU External Sensor status table entry"
	::= { pduExternalSensorNamePlateEntry 1 }

pduExternalSensorNamePlateName  OBJECT-TYPE
	SYNTAX 	DisplayString
	MAX-ACCESS  	read-write
	STATUS 	current
	DESCRIPTION 
		"A user-defined string identifying the external sensor"
	::= { pduExternalSensorNamePlateEntry 2 }

pduExternalSensorNamePlateDescription  OBJECT-TYPE
	SYNTAX 	DisplayString
	MAX-ACCESS  	read-write
	STATUS 	current
	DESCRIPTION 
		"A user-defined description of the external sensor"
	::= { pduExternalSensorNamePlateEntry 3 }

pduExternalSensorNamePlateLocation  OBJECT-TYPE
	SYNTAX 	DisplayString
	MAX-ACCESS  	read-write
	STATUS 	current
	DESCRIPTION 
		"A user-defined string identifying the location of the PDU"
	::= { pduExternalSensorNamePlateEntry 4 }

pduExternalSensorNamePlateSerialNumber  OBJECT-TYPE
	SYNTAX 	DisplayString
	MAX-ACCESS  	read-only
	STATUS deprecated
	DESCRIPTION 
		"The serial code of the external sensor being queried. 
		 This OID is used to show the product code of the sensor. Additionally, similar information is shown in the OID 'pduExternalSensorNamePlateProductCode'"
	::= { pduExternalSensorNamePlateEntry 5 }

pduExternalSensorNamePlateType  OBJECT-TYPE
	SYNTAX 	INTEGER {
		temperature (1),
		humidity (2),
		doorSwitch (3),
		dryContact (4),
		spotFluid (5),
		ropeFluid (6),
		smoke (7),
		beacon (8),
		airVelocity (9),
		modbusAdapter (17),
		hidAdapter (18)
	}
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"The type of external sensor."
	::= { pduExternalSensorNamePlateEntry 6 }

pduExternalSensorNamePlateUnits  OBJECT-TYPE
	SYNTAX 	INTEGER {
		logic (0),
		degreeC (1),
		degreeF (2),
		percent (3),
		mps (4)
	}
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"The base units the external sensor is measured in. 
		This parameter does not apply to onOff, trip, vibration,
		 waterDetection, smokeDetection sensors. "
	::= { pduExternalSensorNamePlateEntry 7 }

pduExternalSensorNamePlateIdentifier  OBJECT-TYPE
	SYNTAX 	Integer32
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"Unique identifier of the external sensor."
	::= { pduExternalSensorNamePlateEntry 8 }
	
pduExternalSensorNamePlateProductCode  OBJECT-TYPE
	SYNTAX 	DisplayString
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"The product code of the external sensor being queried"
	::= { pduExternalSensorNamePlateEntry 9 }

pduExternalSensorConfigTable  OBJECT-TYPE
	SYNTAX SEQUENCE OF PduExternalSensorConfigEntry
	MAX-ACCESS  	not-accessible
	STATUS 	current
	DESCRIPTION 
		"A table of PDU External Sensor configuration data"
	::= { pduExternalSensor 3 }

pduExternalSensorConfigEntry  OBJECT-TYPE
	SYNTAX 	PduExternalSensorConfigEntry
	MAX-ACCESS  	not-accessible
	STATUS 	current
	DESCRIPTION 
		"Configuration data from the PDU External 
		Sensor being queried"
	INDEX { pduUnitConfigIndex, pduExternalSensorConfigIndex }
	::= { pduExternalSensorConfigTable 1 }

PduExternalSensorConfigEntry ::= SEQUENCE {
	pduExternalSensorConfigIndex
		Integer32,
	pduExternalSensorConfigLowerCriticalThreshold
		Unsigned32,
	pduExternalSensorConfigLowerWarningThreshold
		Unsigned32,
	pduExternalSensorConfigUpperCriticalThreshold
		Unsigned32,
	pduExternalSensorConfigUpperWarningThreshold
		Unsigned32,
	pduExternalSensorConfigEnabledThresholds
		BITS,
	pduExternalSensorConfigAlarmState
		INTEGER,
	pduExternalSensorConfigAlarmResetThreshold
		Unsigned32,
	pduExternalSensorConfigAlarmStateChangeDelay
		Unsigned32,
	}

pduExternalSensorConfigIndex  OBJECT-TYPE
	SYNTAX 	Integer32 (0..255)
	MAX-ACCESS  	not-accessible
	STATUS 	current
	DESCRIPTION 
		"The index of the PDU External Sensor 
		configuration table entry"
	::= { pduExternalSensorConfigEntry 1 }

pduExternalSensorConfigLowerCriticalThreshold  OBJECT-TYPE
	SYNTAX 	Unsigned32
	MAX-ACCESS  	read-write
	STATUS 	current
	DESCRIPTION 
		"User-defined lower critical alarm threshold in pduExternalSensorNamePlateUnits."
	::= { pduExternalSensorConfigEntry 2 }

pduExternalSensorConfigLowerWarningThreshold  OBJECT-TYPE
	SYNTAX 	Unsigned32
	MAX-ACCESS  	read-write
	STATUS 	current
	DESCRIPTION 
		"User-defined lower non-critical (warning) alarm threshold in pduExternalSensorNamePlateUnits."
	::= { pduExternalSensorConfigEntry 3 }

pduExternalSensorConfigUpperCriticalThreshold  OBJECT-TYPE
	SYNTAX 	Unsigned32
	MAX-ACCESS  	read-write
	STATUS 	current
	DESCRIPTION 
		"User-defined upper critical alarm threshold in pduExternalSensorNamePlateUnits."
	::= { pduExternalSensorConfigEntry 4 }

pduExternalSensorConfigUpperWarningThreshold  OBJECT-TYPE
	SYNTAX 	Unsigned32
	MAX-ACCESS  	read-write
	STATUS 	current
	DESCRIPTION 
		"User-defined upper non-critical (warning) alarm threshold in pduExternalSensorNamePlateUnits."
	::= { pduExternalSensorConfigEntry 5 }

pduExternalSensorConfigEnabledThresholds  OBJECT-TYPE
	SYNTAX 	BITS {
		lowerCritical (0),
		lowerWarning (1),
		upperWarning (2),
		upperCritical (3),
		binarySensorAlarm (4)
	}
	MAX-ACCESS  	read-write
	STATUS 	current
	DESCRIPTION 
		"A bit string indicating which alarm 
		thresholds are enabled."
	::= { pduExternalSensorConfigEntry 6 }

pduExternalSensorConfigAlarmState OBJECT-TYPE
	SYNTAX 	INTEGER {
		on (1),
		off (0)
	}
	MAX-ACCESS  	read-write
	STATUS 	current
	DESCRIPTION 
		"User defined alarm state of external sensor"
	::= { pduExternalSensorConfigEntry 7 }
	
pduExternalSensorConfigAlarmResetThreshold  OBJECT-TYPE
	SYNTAX 	Unsigned32
	MAX-ACCESS  	read-write
	STATUS 	current
	DESCRIPTION 
		"The hysteresis used for deassertions."
	::= { pduExternalSensorConfigEntry 8 }

pduExternalSensorConfigAlarmStateChangeDelay  OBJECT-TYPE
	SYNTAX 	Unsigned32
	MAX-ACCESS  	read-write
	STATUS 	current
	DESCRIPTION 
		"The delay measured in samples before a state is 
		asserted. If the value is zero, then the state is 
		asserted as soon as it is detected; if it is non-zero, 
		say n, then the assertion condition must exist for n+1 
		consecutive samples before the corresponding assertion 
		event is reported."
	::= { pduExternalSensorConfigEntry 9 }

	
pduExternalSensorStatusTable  OBJECT-TYPE
	SYNTAX SEQUENCE OF PduExternalSensorStatusEntry
	MAX-ACCESS  	not-accessible
	STATUS 	current
	DESCRIPTION 
		"A table of PDU External Sensor status data"
	::= { pduExternalSensor 4 }
	
pduExternalSensorStatusEntry  OBJECT-TYPE
	SYNTAX 	PduExternalSensorStatusEntry
	MAX-ACCESS  	not-accessible
	STATUS 	current
	DESCRIPTION 
		"Status data from the PDU External Sensor 
		being queried"
	INDEX { pduUnitStatusIndex, pduExternalSensorStatusIndex }
	::= { pduExternalSensorStatusTable 1 }

PduExternalSensorStatusEntry ::= SEQUENCE {
	pduExternalSensorStatusIndex
		Integer32,
	pduExternalSensorStatusName
		DisplayString,
	pduExternalSensorStatusCommStatus
		INTEGER,
	pduExternalSensorStatusState
		INTEGER,
	pduExternalSensorStatusValue
		Integer32,
	pduExternalSensorStatusTimeStamp
		DisplayString,
	pduExternalSensorStatusHighPrecisionValue
		Integer32,
	pduExternalSensorSTATUSAisle
		INTEGER
	}

pduExternalSensorStatusIndex  OBJECT-TYPE
	SYNTAX 	Integer32 (0..255)
	MAX-ACCESS  	not-accessible
	STATUS 	current
	DESCRIPTION 
		"The index of the PDU External Sensor status table entry"
	::= { pduExternalSensorStatusEntry 1 }

pduExternalSensorStatusName  OBJECT-TYPE
	SYNTAX 	DisplayString
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"The user-defined name for the External Sensor"
	::= { pduExternalSensorStatusEntry 2 }

pduExternalSensorStatusCommStatus  OBJECT-TYPE
	SYNTAX 	INTEGER {
		notInstalled (1),
		commsOk (2),
		commsLost (3)
	}
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"The communications status of the sensor"
	::= { pduExternalSensorStatusEntry 3 }

pduExternalSensorStatusState  OBJECT-TYPE
	SYNTAX 	INTEGER {
		notPresent (0), alarmed (1), normal (2), belowLowerCritical (3), belowLowerWarning (4), aboveUpperWarning (5), aboveUpperCritical (6)
	}
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"This OID reports the current state of the sensor. 
			A notPresent (0) response indicates that no sensor is attached.
			An alarmed (1) response indicates that the sensor is present 
			and its measured reading indicates alarmed.
			A normal (2) response indicates that the sensor is present 
			and its measured reading lies within all thresholds.
			A belowLowerCritical (3) response indicates that the sensor 
			is present and its measured reading lies below the lower critical threshold.
			A belowLowerWarning (4) response indicates that the sensor 
			is present and its measured reading lies below the lower warning threshold.
			An aboveUpperWarning (5) response indicates that the sensor 
			is present and its measured reading lies above the upper warning threshold.
			An aboveUpperCritical (6) response indicates that the sensor 
			is present and its measured reading lies above the upper critical threshold."
	::= { pduExternalSensorStatusEntry 4 }

pduExternalSensorStatusValue  OBJECT-TYPE
	SYNTAX 	Integer32
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"Sensor reading in pduExternalSensorConfigUnits value."
	::= { pduExternalSensorStatusEntry 5 }

pduExternalSensorStatusTimeStamp  OBJECT-TYPE
	SYNTAX 	DisplayString
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"The sensor reading timestamp."
	::= { pduExternalSensorStatusEntry 6 }

pduExternalSensorStatusHighPrecisionValue  OBJECT-TYPE
	SYNTAX 	Integer32
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"Temperature sensor reading in tenths of pduExternalSensorConfigUnits value.
		This OID is applied to temperature sensor only"
	::= { pduExternalSensorStatusEntry 7 }
	
pduExternalSensorSTATUSAisle  OBJECT-TYPE
	SYNTAX 	INTEGER {
		hotAisle (1),
		coldAisle (2)
	}
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"Indicates whether the external sensor is 
		in a hot or cold aisle"
	::= { pduExternalSensorStatusEntry 8 }

--  Smart Cabinet

pduUnitSmartCabinetTableSize  OBJECT-TYPE
	SYNTAX 	Integer32 (0..255)
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"The total number of Smart Cabinet Configuration "
	::= { pduSmartCabinet 1 }

pduUnitSmartCabinetTable  OBJECT-TYPE
	SYNTAX SEQUENCE OF PduUnitSmartCabinetEntry
	MAX-ACCESS  	not-accessible
	STATUS 	current
	DESCRIPTION 
		"A table of Smart Cabinet information"
	::= { pduSmartCabinet 2 }


pduUnitSmartCabinetEntry  OBJECT-TYPE
	SYNTAX 	PduUnitSmartCabinetEntry
	MAX-ACCESS  	not-accessible
	STATUS 	current
	DESCRIPTION 
		"Information of Smart Cabinet"
	INDEX { pduUnitSmartCabinetIndex }
	::= { pduUnitSmartCabinetTable 1 }

PduUnitSmartCabinetEntry ::= SEQUENCE {
	pduUnitSmartCabinetIndex
		Integer32,
	pduUnitSmartCabinetCardUserName
		DisplayString,
	pduUnitSmartCabinetCardID
		Integer32,
	pduUnitSmartCabinetTimestamp
		DisplayString,
	pduUnitSmartCabinetDoor
		INTEGER
	}

pduUnitSmartCabinetIndex   OBJECT-TYPE
	SYNTAX 	Integer32 (1..256)
	MAX-ACCESS  	not-accessible
	STATUS 	current
	DESCRIPTION 
		"The index of the PDU Smart Cabinet table entry"
	::= { pduUnitSmartCabinetEntry 1 }

pduUnitSmartCabinetCardUserName     OBJECT-TYPE
	SYNTAX 	DisplayString
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"User name of ID card"
	::= { pduUnitSmartCabinetEntry 2 }

pduUnitSmartCabinetCardID		OBJECT-TYPE
	SYNTAX 	Integer32
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"Card ID."
	::= { pduUnitSmartCabinetEntry 3 }

pduUnitSmartCabinetTimestamp	OBJECT-TYPE
	SYNTAX 	DisplayString
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"Indicates the date and time of information update"
	::= { pduUnitSmartCabinetEntry 4 }

pduUnitSmartCabinetDoor	OBJECT-TYPE
	SYNTAX 	INTEGER {
		hotAisle (1),
		coldAisle (2) }
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"Aisle of Smart Cabinet. "
	::= { pduUnitSmartCabinetEntry 5 }
		
pduUnitSmartCabinetControl  	OBJECT IDENTIFIER ::= { pduSmartCabinet 3 }

pduUnitSmartCabinetControlUserName  OBJECT-TYPE
	SYNTAX 	DisplayString
	MAX-ACCESS  	read-write
	STATUS 	current
	DESCRIPTION 
		"User name of ID card"
	::= { pduUnitSmartCabinetControl 1 }

pduUnitSmartCabinetControlCardID		OBJECT-TYPE
	SYNTAX 	Integer32
	MAX-ACCESS  	read-write
	STATUS 	current
	DESCRIPTION 
		"Card ID."
	::= { pduUnitSmartCabinetControl 2 }

pduUnitSmartCabinetControlTimestamp	OBJECT-TYPE
	SYNTAX 	DisplayString
	MAX-ACCESS  	read-write
	STATUS 	current
	DESCRIPTION 
		"Indicates the date and time of information update"
	::= { pduUnitSmartCabinetControl 3 }
	
pduUnitSmartCabinetControlDoor	OBJECT-TYPE
	SYNTAX 	INTEGER {
		hotAisle (1),
		coldAisle (2)
	}
	MAX-ACCESS  	read-write
	STATUS 	current
	DESCRIPTION 
		"Aisle of Smart Cabinet. "
	::= { pduUnitSmartCabinetControl 4 }
	
pduUnitSmartCabinetCardIDEdit	OBJECT-TYPE
	SYNTAX 	INTEGER {
		grant (0), remove (1)
	}
	MAX-ACCESS  	read-write
	STATUS 	current
	DESCRIPTION 
		"Smart Cabinet edit CardID "
	::= { pduUnitSmartCabinetControl 5 }
	
pduUnitSmartCabinetColdAisleLockStatus	OBJECT-TYPE
	SYNTAX 	INTEGER {
		unlock (0), lock (1), notPresent (2)
	}
	MAX-ACCESS  	read-write
	STATUS 	current
	DESCRIPTION 
		"Smart Cabinet ColdAisle lock state "
	::= { pduUnitSmartCabinetControl 6 }

pduUnitSmartCabinetHotAisleLockStatus	OBJECT-TYPE
	SYNTAX 	INTEGER {
		unlock (0), lock (1), notPresent (2)
	}
	MAX-ACCESS  	read-write
	STATUS 	current
	DESCRIPTION 
		"Smart Cabinet HotAisle lock state "
	::= { pduUnitSmartCabinetControl 7 }	

pduUnitSmartCabinetLockStateTable  OBJECT-TYPE
	SYNTAX SEQUENCE OF PduUnitSmartCabinetLockStateEntry
	MAX-ACCESS  	not-accessible
	STATUS 	current
	DESCRIPTION 
		"A table of Smart Cabinet aisle state control"
	::= { pduSmartCabinet 4 }

pduUnitSmartCabinetLockStateEntry  OBJECT-TYPE
	SYNTAX 	PduUnitSmartCabinetLockStateEntry
	MAX-ACCESS  	not-accessible
	STATUS 	current
	DESCRIPTION 
		"Information of Smart Cabinet Lock State"
	INDEX { pduUnitSmartCabinetLockStateIndex }
	::= { pduUnitSmartCabinetLockStateTable 1 }

PduUnitSmartCabinetLockStateEntry ::= SEQUENCE {
  pduUnitSmartCabinetLockStateIndex
  	Integer32,
	pduUnitSmartCabinetColdAisleLockState
		INTEGER,
	pduUnitSmartCabinetHotAisleLockState
		INTEGER,
	pduUnitSmartCabinetColdAisleLockLabel
		DisplayString,
	pduUnitSmartCabinetHotAisleLockLabel
		DisplayString
	}
	
pduUnitSmartCabinetLockStateIndex   OBJECT-TYPE
	SYNTAX 	Integer32 (1..256)
	MAX-ACCESS  	not-accessible
	STATUS 	current
	DESCRIPTION 
		"The index of the PDU Smart Cabinet table entry"
	::= { pduUnitSmartCabinetLockStateEntry 1 }	

pduUnitSmartCabinetColdAisleLockState	OBJECT-TYPE
	SYNTAX 	INTEGER {
		unlock (0), lock (1), notPresent (2)
	}
	MAX-ACCESS  	read-write
	STATUS 	current
	DESCRIPTION 
		"Smart Cabinet ColdAisle lock state "
	::= { pduUnitSmartCabinetLockStateEntry 2 }

pduUnitSmartCabinetHotAisleLockState	OBJECT-TYPE
	SYNTAX 	INTEGER {
		unlock (0), lock (1), notPresent (2)
	}
	MAX-ACCESS  	read-write
	STATUS 	current
	DESCRIPTION 
		"Smart Cabinet HotAisle lock state "
	::= { pduUnitSmartCabinetLockStateEntry 3 }		

pduUnitSmartCabinetColdAisleLockLabel  OBJECT-TYPE
	SYNTAX 	DisplayString
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"Label of cold aisle smartcabinet"
	::= { pduUnitSmartCabinetLockStateEntry 4 }
				
pduUnitSmartCabinetHotAisleLockLabel  OBJECT-TYPE
	SYNTAX 	DisplayString
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"Label of hot aisle smartcabinet"
	::= { pduUnitSmartCabinetLockStateEntry 5 }				
				
-- Traps Information
trapsInfo  OBJECT IDENTIFIER ::= { pduTraps 1 }

trapsInfoTable  OBJECT-TYPE
	SYNTAX SEQUENCE OF TrapsInfoEntry
	MAX-ACCESS  	not-accessible
	STATUS 	current
	DESCRIPTION 
       "A list of Trap Information entries. The number of
            entries are given by the value of pduUnitTableSize."	
	::= { trapsInfo 1 }
	
trapsInfoEntry  OBJECT-TYPE
	SYNTAX 	TrapsInfoEntry
	MAX-ACCESS  	not-accessible
	STATUS 	current
	DESCRIPTION 
		"An entry containing objects used in traps"
	INDEX { trapsInfoIndex }
	::= { trapsInfoTable 1 }

TrapsInfoEntry ::= SEQUENCE {
	trapsInfoIndex
		Integer32,
	userName
		DisplayString,
	userUpdated
		DisplayString,
	firmwareVersion
		DisplayString,
	roleUpdated
		DisplayString,
	smtpRecipients
		DisplayString,
	smtpServer
		DisplayString
	}

trapsInfoIndex  OBJECT-TYPE
	SYNTAX 	Integer32 (1..256)
	MAX-ACCESS  	not-accessible
	STATUS 	current
	DESCRIPTION 
		"The index of the traps table entry"
	::= { trapsInfoEntry 1 }


userName  OBJECT-TYPE
	SYNTAX 	DisplayString
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"The user currently logged in."
	::= { trapsInfoEntry 2 }
	
userUpdated  OBJECT-TYPE
	SYNTAX 	DisplayString
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"The user added, deleted, or modified."
	::= { trapsInfoEntry 3 }

firmwareVersion  OBJECT-TYPE
	SYNTAX 	DisplayString
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"The version of Firmware."
	::= { trapsInfoEntry 4 }

roleUpdated  OBJECT-TYPE
	SYNTAX 	DisplayString
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"The role added, deleted, or modified."
	::= { trapsInfoEntry 5 }

smtpRecipients  OBJECT-TYPE
	SYNTAX 	DisplayString
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"Comma separated list of SMTP  recipients"
	::= { trapsInfoEntry 6 }

smtpServer  OBJECT-TYPE
	SYNTAX 	DisplayString
	MAX-ACCESS  	read-only
	STATUS 	current
	DESCRIPTION 
		"The IP address/host name of the SMTP server"
	::= { trapsInfoEntry 7 }

pduIndex  OBJECT-TYPE
	SYNTAX 	Integer32
	MAX-ACCESS  	accessible-for-notify
	STATUS 	current
	DESCRIPTION 
		"A unique value for PDU. Its value ranges between 1 
		and the value of PDU count"
	::= { trapsInfo 2 }

externalSensorIndex  OBJECT-TYPE
	SYNTAX 	Integer32
	MAX-ACCESS  	accessible-for-notify
	STATUS 	current
	DESCRIPTION 
		"A unique value for each sensor. Its value ranges between 1 
		and the value of external sensor count."
	::= { trapsInfo 3 }

serverPing  OBJECT-TYPE
	SYNTAX 	INTEGER {
		pingEnable (1),
		pingDisable (2),
		serverReachable (3),
		serverNotReachable (4)
	}
	MAX-ACCESS  	accessible-for-notify
	STATUS 	current
	DESCRIPTION 
		"Whether server ping has been enabled or disabled and 
		whether the server is reachable or not reachable"
	::= { trapsInfo 4 }

usbDevice  OBJECT-TYPE
	SYNTAX 	INTEGER {
		connected (1),
		disconnected (2)
	}
	MAX-ACCESS  	accessible-for-notify
	STATUS 	current
	DESCRIPTION 
		"Whether a USB device has been connected or disconnected"
	::= { trapsInfo 5 }

errorDescription  OBJECT-TYPE
	SYNTAX 	DisplayString
	MAX-ACCESS  	accessible-for-notify
	STATUS 	current
	DESCRIPTION 
		"Description of the Error"
	::= { trapsInfo 6 }

cascading  OBJECT-TYPE
	SYNTAX 	INTEGER {
		connected (1),
		disconnected (2)
	}
	MAX-ACCESS  	accessible-for-notify
	STATUS 	current
	DESCRIPTION 
		"Whether a cascading member has been connected or disconnected"
	::= { trapsInfo 7 }

systemCommunication  OBJECT-TYPE
	SYNTAX 	INTEGER {
		ok (1),
		lost (2)
	}
	MAX-ACCESS  	accessible-for-notify
	STATUS 	current
	DESCRIPTION 
		"Whether the Network management card has lost contact with cascading member."
	::= { trapsInfo 8 }

trapCode OBJECT-TYPE
	SYNTAX INTEGER
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"A number identifying the event for the trap that was sent.
		 Mapped unique trap code per unique event to be used by ISEE's
		 decoder ring."
	::= { trapsInfo 9 }

trapDescription OBJECT-TYPE
	SYNTAX DisplayString (SIZE (0..255))
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"A string identifying the event for that last trap that was sent."
	::= { trapsInfo 10 }


trapCritical 			NOTIFICATION-TYPE
				OBJECTS  {
						 trapCode, 
						 trapDescription, 
						 sysDescr, 
						 pduNamePlateIPAddress}
        		STATUS      current
				DESCRIPTION
        			"A critical alarm has occurred."
        		::= {pduTraps  1}

trapWarning 			NOTIFICATION-TYPE
				OBJECTS  { 
					     trapCode, 
					     trapDescription, 
					     sysDescr, 
					     pduNamePlateIPAddress}
				STATUS      current
				DESCRIPTION
				"A warning alarm has occurred."
				::= {pduTraps  2}

trapInformation 		NOTIFICATION-TYPE
				OBJECTS  {
					     trapCode, 
					     trapDescription, 
					     sysDescr, 
					     pduNamePlateIPAddress }
				STATUS      current
				DESCRIPTION
				"An informational alarm has occurred."
				::= {pduTraps  3}

trapCleared 			NOTIFICATION-TYPE
				OBJECTS  {
					     trapCode, 
					     trapDescription, 
					     sysDescr, 
					     pduNamePlateIPAddress}
				STATUS      current
				DESCRIPTION
				"An alarm has cleared."
				::= {pduTraps  4}

trapTest 			NOTIFICATION-TYPE
				OBJECTS  {
					     trapCode,
				             trapDescription,
					     sysDescr, 
					     pduNamePlateIPAddress} 
				STATUS      current
				DESCRIPTION
				"Test trap sent to a trap receiver to check proper reception of traps" 
				::= {pduTraps  5}

--     ======Ehandle Sensor Status==========
pduEhandleTable OBJECT-TYPE
    SYNTAX SEQUENCE OF PduEhandleEntry
    ACCESS not-accessible
    STATUS mandatory
    DESCRIPTION
        "A list of contact sensors.  The number of entries are
         given by number of pdu and pduEhandleCount."
    ::= { pduEhandle 1 }

pduEhandleEntry OBJECT-TYPE
    SYNTAX PduEhandleEntry
    ACCESS not-accessible
    STATUS mandatory
    DESCRIPTION
        "An entry for a contact sensor"
    INDEX { pduEhandleIndex }
    ::= { pduEhandleTable 1 }

PduEhandleEntry ::= SEQUENCE
    {
        pduEhandleIndex              INTEGER,
        pduEhandleAisle              INTEGER,
        pduEhandleHandleOperation    INTEGER,
        pduEhandleFwVer                  DisplayString,
        pduEhandleMechanicalLock        INTEGER,
        pduEhandleSerial               DisplayString,
        pduEhandleHwVer                DisplayString,
        pduEhandleAutoLockTime       INTEGER,
        pduEhandleDoorOpenTime       INTEGER,
        pduEhandleMaxDoorOpenTime    INTEGER,
        pduEhandleUserPinLength      INTEGER,
        pduEhandleUserPinMode        INTEGER,
        pduEhandleAisleControl       INTEGER
     }

pduEhandleIndex OBJECT-TYPE
    SYNTAX INTEGER (1..2)
    ACCESS read-only
    STATUS mandatory
    DESCRIPTION
        "The index of the PDU HID table entry"
    ::= { pduEhandleEntry 1 }

pduEhandleAisle OBJECT-TYPE
    SYNTAX INTEGER
        {
            hot(1),
            cold(2)
        }
    ACCESS read-only
    STATUS mandatory
    DESCRIPTION
        "Aisle of HID handle. "
    ::= { pduEhandleEntry 2 }

pduEhandleHandleOperation OBJECT-TYPE
    SYNTAX INTEGER
        {
            unlock(1),
            lock(2)
        }
    ACCESS read-write
    STATUS mandatory
    DESCRIPTION
        "HID handle control opterations "
    ::= { pduEhandleEntry 3 }

pduEhandleFwVer OBJECT-TYPE
    SYNTAX DisplayString
    ACCESS read-only
    STATUS mandatory
    DESCRIPTION
        "The firmware revision level of the HID"
    ::= { pduEhandleEntry 4 }

pduEhandleMechanicalLock OBJECT-TYPE
    SYNTAX INTEGER
        {
            unlock(1),
            lock(2)
        }
    ACCESS read-only
    STATUS mandatory
    DESCRIPTION
        "HID Mechanical opterations "
    ::= { pduEhandleEntry 5 }

pduEhandleSerial OBJECT-TYPE
    SYNTAX DisplayString
    ACCESS read-only
    STATUS mandatory
    DESCRIPTION
        "The Serial Number of the HID"
    ::= { pduEhandleEntry 6 }

pduEhandleHwVer OBJECT-TYPE
    SYNTAX DisplayString
    ACCESS read-only
    STATUS mandatory
    DESCRIPTION
        "The hardware revision level of the HID"
    ::= { pduEhandleEntry 7 }

pduEhandleAutoLockTime OBJECT-TYPE
SYNTAX INTEGER
    ACCESS read-write
    STATUS mandatory
    DESCRIPTION
        "HID Electronic Latch Autolock Time in seconds, Value ranges (0-999) "
::= { pduEhandleEntry 8 }

pduEhandleDoorOpenTime OBJECT-TYPE
    SYNTAX INTEGER
    ACCESS read-write
    STATUS mandatory
    DESCRIPTION
        "HID Door Open Time in seconds, Value ranges (0-999)"
        ::= { pduEhandleEntry 9 }

pduEhandleMaxDoorOpenTime OBJECT-TYPE
    SYNTAX INTEGER
    ACCESS read-write
    STATUS mandatory
    DESCRIPTION
        "HID Max Door Open Time in seconds, Value ranges (0-32400),
         critical alarm will be raised if door is left open past this time"
    ::= { pduEhandleEntry 10 }

pduEhandleUserPinLength OBJECT-TYPE
    SYNTAX INTEGER
    ACCESS read-write
    STATUS mandatory
    DESCRIPTION
        "Rack Access User minimum PIN Length, value ranges(1-15)"
    ::= { pduEhandleEntry 11 }

pduEhandleUserPinMode OBJECT-TYPE
    SYNTAX INTEGER
        {
            visible(1),
            hidden (2)
        }
    ACCESS read-write
    STATUS mandatory
    DESCRIPTION
        "Rack Access User PIN mode setting"
    ::= { pduEhandleEntry 12 }

pduEhandleAisleControl OBJECT-TYPE
    SYNTAX INTEGER
        {
            combined (1),
            standalone(2)
        }
    ACCESS read-write
    STATUS mandatory
    DESCRIPTION
        "Rack Access Aisle Control setting,
         when set to standalone each aisle will controlled seprately,
         when set to combined opposite aisle can be controlled with authenticated control action on either aisle"
    ::= { pduEhandleEntry 13 }


--     ======EHANDLE control table==========
pduEhandleControlTable OBJECT-TYPE
    SYNTAX SEQUENCE OF PduEhandleControlEntry
    ACCESS not-accessible
    STATUS mandatory
    DESCRIPTION
        "A list of smartcard.  The number of entries are
         given by number of pdu and pduEhandleCount."
    ::= { pduEhandle 2 }

pduEhandleControlEntry OBJECT-TYPE
    SYNTAX PduEhandleControlEntry
    ACCESS not-accessible
    STATUS mandatory
    DESCRIPTION
        "The smart card table entry containing the usrname, cardid, cardaisle etc."
    INDEX { pduEhandleControlIndex }
    ::= { pduEhandleControlTable 1 }

PduEhandleControlEntry ::= SEQUENCE
    {
        pduEhandleControlIndex                    INTEGER,
        pduEhandleControlUserName                 DisplayString,
        pduEhandleControlCardIdStr                DisplayString,
        pduEhandleControlTimestamp                DisplayString,
        pduEhandleControlCardAisle                INTEGER,
        pduEhandleControlStartTime                DisplayString,
        pduEhandleControlExpireTime               DisplayString,
        pduEhandleControlTempUser                 INTEGER,
        pduEhandleControlPin                      DisplayString
    }

pduEhandleControlIndex OBJECT-TYPE
    SYNTAX INTEGER (1..200)
    ACCESS read-only
    STATUS mandatory
    DESCRIPTION
        "The index of the PDU smartcard table entry"
    ::= { pduEhandleControlEntry 1 }

pduEhandleControlUserName OBJECT-TYPE
    SYNTAX DisplayString
    ACCESS read-write
    STATUS mandatory
    DESCRIPTION
        "User name of smartcard"
    ::= { pduEhandleControlEntry 2 }

pduEhandleControlCardIdStr	OBJECT-TYPE
    SYNTAX DisplayString
    ACCESS read-write
    STATUS mandatory
    DESCRIPTION
        "smartcard ID."
    ::= { pduEhandleControlEntry 3 }

pduEhandleControlTimestamp OBJECT-TYPE
    SYNTAX DisplayString
    ACCESS read-only
    STATUS mandatory
    DESCRIPTION
        "Indicates the date and time of accessing"
    ::= { pduEhandleControlEntry 4 }

pduEhandleControlCardAisle OBJECT-TYPE
    SYNTAX INTEGER
        {
            hot(1),
            cold(2),
            both (3)
        }
    ACCESS read-write
    STATUS mandatory
    DESCRIPTION
        "Aisle of authorized card"
    ::= { pduEhandleControlEntry 5 }

pduEhandleControlStartTime OBJECT-TYPE
    SYNTAX DisplayString
    ACCESS read-write
    STATUS mandatory
    DESCRIPTION
        "Indicates the start date and time Rack access user is given access"
    ::= { pduEhandleControlEntry 6 }

pduEhandleControlExpireTime OBJECT-TYPE
    SYNTAX DisplayString
    ACCESS read-write
    STATUS mandatory
    DESCRIPTION
        "Indicates the date and time when the access of user card will expire, To set expire time first set user as temporary user"
    ::= { pduEhandleControlEntry 7 }

pduEhandleControlTempUser OBJECT-TYPE
    SYNTAX INTEGER
        {
            no(1),
            yes(2)
        }
    ACCESS read-write
    STATUS mandatory
    DESCRIPTION
        "Indicates if the card user has temporary access"
    ::= { pduEhandleControlEntry 8 }

pduEhandleControlPin OBJECT-TYPE
    SYNTAX DisplayString
    ACCESS read-write
    STATUS mandatory
    DESCRIPTION
        "Rack acess control entry keypad PIN"
    ::= { pduEhandleControlEntry 9 }

-- ++++ End of cPDU ++++


END